This paper investigates the use of a combined hydrogen, heat, and power (CHHP) system for Omar Al-Mukhtar University campus using local resources. Based on previous local resource assessment studies, the hydrogen team of Omar AL-Mukhtar University (OMU) selected the fuelcell energy DFC4000 TM unit. This study shows that the CHHP system can provide electricity to power the university campus, thermal energy for heating the anaerobic digester, and hydrogen for transportation, back-up power and other needs. Consequently, using the alternative fuels and renewable energy resources for OMU campus can lower fossil fuel consumption and, therefore, greenhouse gas emissions (GHG).
OMU campus in El-Beida City is the fourth largest campus in Libya with 1.9 km2 and approximately 7000 students. The university is one of El-Beida’s largest electric power consumers with a peak demand of 13.78 MWe and electric energy consumption of 3 × 105 kWh/day. Currently, electrical power of the university campus is purchased from General Electricity Company of Libya (GECOL) and distributed from the substation and switchgear located at the campus power plant. Biogas produced by anaerobic digestion of wastewater, organic waste, agricultural waste, animal waste, and industrial waste is a potential source of renewable energy. Treated biogas can be used to generate CHHP, using a molten carbonate fuelcell (MCFC) [
Hydrogen team of OMU selected the location of the CHHP plant at OMU campus to be in the southwest side as shown in
This section describes the design of the major components and explains the various processes occurring during system operation. The design discussed in this paper has three major systems: 1) anaerobic digestion system, 2) CHHP system consisting of a DFC4000TM fuelcell unit, and 3) Hydrogen recovery, cleaning, compression, storage, dispensing, and distribution system on university campus from CHHP system [
The anaerobic digestion system and the CHHP system are sized based on the amount of locally available feedstock and the amount of methane gas generated respectively [
Feedstock is collected and transported to the storage facility. The storage facility consists of a 48.22 m × 48.22 m (2325 m2) steel building to protect the feedstock from the elements [
Digesters and biogas production are shown in
The design uses a highly efficient Jet Mix™ Vortex Mixing System by Siemens, to mix the biomass inside the digester. The system suspends organic and inorganic solids with intermittent mixing, making possible power savings of up to 50% or more. The system maintains efficiency regardless of tank level and minimizes dead spots due to its innovative mixing pattern and also has the capability to mix multiple tanks using one central pumping facility. This system will eliminate the use of multiple pumps and will reduce the capital cost of the digester system. The proposed anaerobic digester is sized such that it has retention time of 21 days. The specification and details of the digester are shown in
Tank side water depth | 16 m |
---|---|
Tank wall height (below grade) | 18.25 m |
Tank diameter | 38.125 m |
Cone per tank | 1115 m3 |
Tank wall thickness | 0.30 m |
Floor slope | 1:6 |
Quantity of solids to digester | 36 × 103 kg/day |
Retention time | 21 days |
Volatile solids concentration | 80% |
Anticipated solids reduction | 50% |
Anticipated gas yield | 0.93 m3/kgVS destroyed |
Anticipated biogas production | 550 m3/h |
Volatile solids |
Inside the anaerobic digester, microorganisms act on the organic feedstock to produce biogas; digest ate, and water [
Two main adsorption technologies are being considered: pressure swing adsorption (PSA) and temperature swing adsorption (TSA). The mean difference between the PSA and TSA methods refers to the strategy for regenerating the adsorbent after the adsorption step and the time duration of an individual adsorption circle and adsorption circle in varied temperature technology generally takes several times longer than in varied-pressure technology. On other hand, in PSA applications, the pressure of the bed is reduced, whereas in TSA, the temperature is raised while pressure is maintained approximately constant. In this project, the step time for desorption is of the same order of magnitude as that of the adsorption (sometimes even smaller). Consequently, this process enjoys shorter cycle time and better efficiency also by using Zeolites 13X compared to TSA, and accordingly, is chosen. In addition, the most of studies dealing with CO2 capture use Zeolites 13X as adsorbent in PSA or TSA technologies because Zeolite 13X has high selectivity to CO2.
Biogas from the anaerobic digestion is stored in a buffer tank which supplies biogas to the gas treatment system. The treatment system uses PSA technology to separate methane present in the biogas [
・ The DFC® units cannot accept H2S, water (H2O), and other impurities in its input fuel. Therefore, biogas treatment is necessary before feeding it into the fuelcell under all conditions [
・ Inlet fuel pressure to the fuelcell should be between 2 - 2.4 bars. If the fuel contains 40% carbon dioxide, it will impact the sizing and the equipment downstream the fuelcell of the design will require a higher capacity heat exchanger, water-gas shift reactor, and hydrogen purification or separation system. The DFC4000TM requires 651.1 m3/h of natural gas at 34.65 MJ/m3. If biogas (60% methane and 40% carbon dioxide) is utilized, the fuelcell system will require 477 m3/h of biogas as fuel to operate. This will increase the size of the equipment downstream the fuelcell by 55% and will increase its capital cost which is not desirable [
・ The product gas from the PSA unit is expected to have an average heat content of 34.65 MJ/m3 which is roughly equal to the average heat content of natural gas consumed in OMU (34.65 MJ/m3). Hence, the fuelcell unit will receive a consistent fuel throughout its operation. The process and flow during the biogas treatment is illustrated in
The two anaerobic digesters system will be able to supply 100% of fuel for the DFC4000TM unit from locally available feedstock.
The AOG calculations are remade based on the AOG composition calculation document provided by fuelcell energy [
and that only 65% (the fuel utilization rate) of the H2 produced is reacted at the anode to produce electricity. In order to reflect the AOG composition, it is assumed that one third of the 35% hydrogen produced is back-shifted to produce H2O and CO. Based on these assumptions and the processes taking place inside the fuelcell, the following Equations (1)-(5) for every one mole of methane (CH4) entering the anode side are obtained.
Internal reforming:
CH 4 + 2 H 2 O → 4 H 2 + CO 2 (1)
Assuming one mole of CH4 is fed to the DFC® system; only 65% of the hydrogen (i.e. 2.6 moles) reacts at the anode and will result in the following equation.
Corresponding reaction at anode:
2.6 H 2 + 2.6 CO 3 − − → 2.6 H 2 O + 2.6 CO 2 + 2 e − (2)
The remaining 35% of the H2 (1.4 moles) and the entire CO2 (1 mole) from Equation (1) goes directly to the AOG. Combining the products from (2) and 1.4 moles of H2 and 1 mole of CO2 from (1) results in the following AOG composition.
1.4 H 2 + 2.6 H 2 O + 3.6 CO 2 (3)
But in reality, another internal reaction takes place in the DFC® fuel cell. One third of the H2 in Equation (3) (i.e. 0.47 moles) needs to back-shifted to H2O and CO resulting in Equation (4).
0.47 H 2 + 0.47 CO 2 → 0.47 H 2 O + 0.47 CO (4)
Combining Equations (3) and (4) yields the following products:
0.93 H 2 + 3.07 H 2 O + 0.47 CO + 3.13 CO 2 (5)
The inlet fuel requirement of the DFC4000TM unit based on 156 MJ/m3 input fuel is calculated and found to be 651.1 m3/h. Assuming that the input fuel consists of 98% CH4 and 2% CO2, 651.1 m3/h of fuel consists of 451 moles of CH4 and 9 moles of CO2. The actual AOG flow rate corresponding to 451 moles of methane per minute is calculated using Equation (5).
In order to succeed a CHHP system, hydrogen from the AOG must be recovered, cleaned and distributed from the DFC® fuelcell system. This section explains the hydrogen recovery and water-gas shift reaction for additional hydrogen production, removal and recycling of water, purification of hydrogen gas, and CO2 transfer to the cathode side of the fuelcell [
The AOG outlet pressure is 1.08 bar and outlet temperature to be 600˚C. The AOG is first cooled and pressurized to undergo water-gas shift reaction.
Water-gas shift reaction:
H 2 O + CO → H 2 + CO 2 (6)
The entire CO present in the AOG reacts with H2O to produce an additional 242 kg of H2 and of 4 × 103 kg of CO2 per day. The water vapor is condensed and recycled to the anode side of the fuelcell for the internal reforming of methane. The amount of water produced during condensation is greater than the fuelcell requirement with the excess water is sent into the sewer. The CO2 and H2 coming out of the water-gas shift reactor is cooled and separated using a PSA unit. The hydrogen coming out of the PSA unit is compressed and used for different applications on the university campus. Outside air is preheated using the heat exchanger and is mixed with the CO2 coming out the PSA unit in Anode Gas Oxidizer (AGO). The mixture is then transferred to the cathode to complete the cathode reaction as shown in Equation (7).
Reaction at cathode:
CO 2 + 0.5 O 2 + 2 e − → CO 3 (7)
The flow rates of gases at different stages were estimated and tabulated in
The system will be incorporated into the existing hydrogen infrastructure on the university campus. The existing hydrogen station was designed such that it could handle higher volume of hydrogen in the future. The product hydrogen from the PSA unit will be transferred into the buffer tank located in the adjacent hydrogen station via pipeline. The buffer tank feds two compressors: 1) the existing Hydro-Pac C06-10-70/140LX compressor (415 bars) and 2) the PDC machines (PDC-13-1000-3000) compressor (250 bars). The compressed hydrogen from the Hydro-Pac compressor will be stored in existing storage tanks. Hydrogen from the PDC machine compressor will be used to fill a hydrogen tube trailer and K-cylinder manifold.
This section explains how to use the output from the DFC4000TM fuelcell (Heat, Hydrogen, and Electricity on the campus). Fuelcells operating on methane from biogas offer a pathway to renewable electricity generation Tri-generation of electricity, heat, and hydrogen offers an alternative route to solving the H2 infrastructure problem facing fuelcell vehicle deployment. Consequently, it will be promoting biogas fuelcells in the future under its market transformation programs. Finally, this part gives details for calculation electric, heat recovery, and hydrogen output from the CHHP system.
The electric power output of the DFC4000TM unit operating in the simple cycle CHP mode is 3.7 MWe. This corresponds to the net power after providing the parasitic loads for its Mechanical Balance of the Plant (M-BOP) and energy loss in the Electrical Balance of the Plant (E-BOP). However, there are additional components that require electric power for the DFC4000TM unit operating in CHHP mode. These components, including the heat exchanger for AOG cooling, the water-gas shift reactor, and the PSA unit for hydrogen purification and operate collectively with the fuelcell unit to form the CHHP system. Based on the power requirements of these components, the net power output from the CHHP system was estimated to be 3.2 MWe. The total electric power requirement of different equipment used in the design is estimated to be approximately 474 kWe and is tabulated in
Auxiliary loads include site lighting, safety devices, hydrogen dispenser, and electric loads at central control station. The total net energy production from the CHHP system is 76.8 × 103 kWh per day and the energy demand for on-site use is 8000 kWh per day. Hence, the CHHP system will be able to provide 68.8 × 103 kWh per day to the university campus. This corresponds to 23% of the whole campus electricity requirement.
The DFC4000TM unit has 4GJ/h at 49˚C available for heat recovery while operating in CHP mode. However, the recoverable heat from a DFC4000TM unit operating in CHHP mode is considerably lower than compared to the operating in CHP mode. This is due to the cooling of anode outlet gas, removal of water vapor, hydrogen recovery, and lower flow rate of the exhaust gases. The thermal energy available for heat recovery was calculated based on the cathode exhaust gas composition and Equation (8) is shown in
Q = m × C P ( Δ T ) (8)
where m, CP and ΔT are the mass flow rate of the gas (kg/h), the specific heat of the gas (kJ/kg・K) and the change in temperature of the gas (K) respectively.
The low thermal energy from the DFC4000TM unit can be attributed to the low flow rate of the exhaust gases when compared to the DFC4000TM in CHP cycle. Two components in the system that require heat energy are 1) hygienization unit and 2) anaerobic digester. Hygienization of feedstock prevents pathogens from entering the digester and maintaining optimum temperature inside the anaerobic digester ensures maximum biogas production. The mass of the feedstock and digester sludge that need to be heated are 36 × 103 kg/day and 12 × 106 kg/day, respectively. The temperature of feedstock was assumed to be 20˚C. The digester is heated to 40˚C during its initial fill and is assumed to lose 1˚C on average every hour due to environmental losses.
Gas | HEX W.G. shift inlet (mol/min) | HEX W.G. shift outlet (mol/min) | PSA product outlet (mol/min) | PSA tail gas (mol/min) | AGO inlet (mol/min) | cathode exhaust (mol/min) |
---|---|---|---|---|---|---|
H2 | 356.5 | 536.6 | 483 | 53.6 | 53.6 | 53.6 |
CO2 | 1200.2 | 1380.3 | - | 1380.3 | 1380.3 | 414.1 |
H2O | 1177.2 | 997.2 | - | - | - | - |
CO | 180.2 | - | - | - | - | - |
O2 | - | - | - | - | 690.15 | 207.05 |
N2 | - | - | - | - | 2597 | 2597 |
Equipment | Max. power rating (kWe) | Daily operation Time (h) | Daily energy consumption (kWh) |
---|---|---|---|
Feedstock storage facility | 7 | 12 | 84 |
Macerator | 38 | 4 | 152 |
Screw feeder | 7 | 4 | 28 |
Pump | 100 | 4 | 400 |
Hygienization unit | 9 | 4 | 36 |
Anaerobic digester | 8 | 24 | 192 |
Storage tank | 7 | 24 | 168 |
Biogas PSA unit | 95 | 24 | 2.28 × 103 |
Hydrogen compressor Comp1 | 12.5 | 24 | 300 |
Hydrogen compressor Comp2 | 165 | 24 | 3.96 × 103 |
Auxiliary loads | 25 | 16 | 400 |
Total | 473.5 | 164 | 8,000 |
Gas | Cathode exhaust (kmol/min) | Mass flow rate (kg/h) | Cp (kJ/kg・K) | ΔT (K) | Q flow rate (MJ/h) |
---|---|---|---|---|---|
H2 | 0.054 | 6.41 | 14.32 | 322 | 29.6 |
CO2 | 0.414 | 451.95 | 0.84 | 322 | 122.2 |
O2 | 0.207 | 347.56 | 0.92 | 322 | 103 |
N2 | 2.597 | 4985.1 | 1.04 | 322 | 1669.4 |
Total | 5791.02 | 1924.2 |
Thermal load | Mass flow rate (kg/h) | Cp (kJ/kg・K) | ΔT (K) | Q flow rate (MJ/h) |
---|---|---|---|---|
Hygienization unit | 1500 | 2.3 | 50 | 172.5 |
Anaerobic digester | 500,000 | 4.2 | 1 | 2100 |
Total | 2272.5 |
In this paper the design of a CHHP system for OMU campus using local resources is studied. The study shows that the CHHP system can provide electricity to power the university campus, thermal energy for heating the anaerobic digester, and hydrogen for transportation, back-up power and other needs. The CHHP system will be able to provide approximately 68,800 kWh and 1480 kg/day of hydrogen to the university campus. Ultimately, the CHHP system will reduce energy consumption, fossil fuel usage, and GHG. It will be able to provide approximately 23% of the university campus’s electricity need.