Journal of Power and Energy Engineering, 2015, 3, 250-261
Published Online April 2015 in SciRes. http://www.scirp.org/journal/jpee
http://dx.doi.org/10.4236/jpee.2015.34034
How to cite this paper: Zhu, W.P., Wang, Z.C., Yuan, X.D. and Fan, R.N. (2015) Security Assessment of Distribution System
with Distributed Photovoltaic. Journal of Power and Energy Engineering, 3, 250-261.
http://dx.doi.org/10.4236/jpee.2015.34034
Security Assessment of Distribution System
with Distributed Photovoltaic
Weiping Zhu1, Zhicheng Wang2, Xiaodong Yuan1, Ruonan Fan3*
1Jiangsu Electric Power Company Research Institute, Jiangsu, China
2State Grid Jiangsu Electric Power Company, Jiangsu, China
3Photovoltaic System Research Center of Ministry of Education, Hefei University of Technology, Hefei, China
Email: *2851619 43@qq .com
Received January 2015
Abstract
In order to evaluate the safe and stable operation of distribution network with the distributed
photovoltaic (PV), the security of distribution network is researched. On the basis of electricity
supply security, voltage quality and network losses, the index system of static security is estab-
lished. The paper simulates the uncertainty and random characteristics of PV by OpenDSS. The
typical scenes that PV accessed to the distribution network are designed. The paper summarizes
the results of voltage fluctuation and network losses and uses indices to quantify it under different
scenes. Based on the index system, the paper proposes some recommendations on PV permeabili-
ty, interconnected locations, dispersion degrees and power factors when the distributed PV ac-
cessed to the distribution network.
Keywords
Distributed PV, Static Security, Index System, Voltage Fluctuation, Network Losses
1. Introduction
In recent years, the proportion of PV generation in the power industry is increasing heavily. With the continuous
development of large-scale grid-connected PV, the research on security of distribution network with distributed
PV is becoming increasingly important. A large quantity of distributed PV accessed to the distribution network,
transforms traditional signal power network into multiport grid and the direction of power flow becomes mul-
tiple. PV generation is volatile and has low density and self-adjustment abilities, its power generation is affected
by temperature, irradiance and other factors. So the fluctuation and randomness of output power are large and
have a significant impact on the safe operation of the distribution network. Therefore, it is important to research
the security of the distribution network with modularized distributed PV.
At present, most security studies of distribution network with distributed PV are based on post-fault analyses.
Reference [1] proposes some assessment indices based on the security rules of K(N 1 + 1), and fuzzy com-
prehensive model is used to evaluate the safety; considering the risk theory, reference [2] proposes the risk indi-
*Corresponding author.
W. P. Zhu et al.
251
cators of load losses, overload and voltage limit violation. The evaluations of operation process are too little to
evaluate the influences of PV on distribution network and can’t give advices for reasonable planning of power
system. Reference [3] analyzes the impacts caused by grid-connected PV on distribution network voltages and
losses in mechanism. The peak capacity of distributed PV source with constraint of over-voltage is researched in
[4].
Firstly, the paper proposes an index system of static security assessment. The randomness of PV generation is
simulated by OpenDSS. In addition, the typical scenes that PV accessed to the distribution network are designed
to analyze the influences of network’s normal operation ratio, voltage fluctuation and network losses under dif-
ferent capacities, interconnected locations, dispersion conditions and power factors of grid-connected PV. The
voltage fluctuation indices and mitigation degree of network losses are calculated. Finally, to improve the safety
and stability of distribution network and reduce the network losses, the paper proposes some advices on different
conditions that PV accessed to the distribution network such as PV permeability and interconnected locations.
2. Index System of Static Security Assessment
Distribution network static security is used to judge whether the abnormal status occur under certain operation
conditions, such as over voltage, lines and components overload [5]. The paper assesses the static security on the
basis of electricity supply security, voltage quality and network losses.
Firstly, the normal operation ratio index is calculated. Ensure that the distribution network system is in normal
operation condition and then evaluate the voltage quality and network losses by other indices. The grid-con-
nected PV changes the power flow of distribution network, because of the reduction of feeder transmission
power and the reactive power generated by PV, the node voltage will increase and the voltage fluctuation will
change [6]. Thus this paper measures the voltage quality mainly from voltage fluctuation ratio. The active and
reactive power of the line varies widely when different capacities, locations, dispersion degrees and power fac-
tors of PV which accessed to the distribution network. The network losses which mainly depend on system
power flow will be affected inevitably by the access of PV [7]. The network losses indices include percentage of
power losses and mitigation degree of network losses. The mitigation degree of network losses reflects the im-
provement levels of network losses under different access conditions [8]-[10].
The static security indices are shown as Figure 1 below.
2.1. Normal Operation Ratio E
Normal operation ratio E is introduced for judging whether the feeder current exceeds the normal allowable
current.
100%
N
I
EI
= ×
( 1)
where, I is feeder current and
N
I
is normal allowable current.
Too heavy loads of the distribution network will lead to the excessive current. It’s easy to cause the overload
phenomenon when the current exceeds the normal allowable value. Higher the value of E, more load demands
Static security
Electricity
supply security
Voltage quality
Network losses
Normal Operation Ratio
Voltage Fluctuation Ratio
Average of Voltage Fluctuation
Ratio
Percentage of Power Losses
Mitigation degree of network
losses
Figure 1. Index system of static security.
W. P. Zhu et al.
252
the network meet.
2.2. Voltage Fluctuation Ratio ΔV%
Voltage Fluctuation Ratio is introduced to study the effects of PV on voltage fluctuation.
()( )
( )
%
1100%
1
aa
a
Vt Vt
VVt
−−
∆= ×
(2)
where,
( )
a
Vt
and
are one node’s voltage of adjacent time.
Voltage fluctuation ratio describes one node’s voltage fluctuation levels for some time. The ratio is higher, the
fluctuation is larger, and the stability of distribution network will have big changes.
2.3. Average of Voltage Fluctuation Ratio EΔV%
%%
1
1n
V
EV
n
= ∆
(3)
The grid-connected PV has great influences on voltage fluctuation of distribution network, especially when
PV puts into operation or breaks off from the network. The influences also depend on the capacities, locations,
power factors of PV and topologies of distribution networks, the assessment of voltage fluctuation is more dif-
ficult. Thus the average of voltage fluctuation ratio is introduced to evaluate the overall levels of voltage fluctu-
ation under different access situations.
2.4. Percentage of Power Losses Ploss%
loss
loss
%P
PP
=
(4)
where, Ploss is total losses and P is total load power.
2.5. Mitigation Degree of Network Losses M
PV
MWW
W
=
(5)
where,
W
is total losses of distribution network without grid-connected PV, WPV is total losses after PV ac-
cessed to the distribution network.
The value of M is higher, the network losses is smaller. It indicated that grid-connected PV leads to better re-
duction of network losses.
3. Models of Security Assessment Based on OpenDSS
Facing with distribution network’s functional requirements of fast simulation, American Electric Power Re-
search Institute provides the OpenDSS software to support the design, planning, operation and research of dis-
tribution system. OpenDSS has a variety of network models, can realize fast and stable power flow calculation
and shows the nice convergence property and fast calculation speed. It also applies to power flow calculation for
large-scale distribution network. In addition, the user can realize further extending application and analysis
through the COM interface. OpenDSS provides an open and sharing software platform for smart grid and plays
an important role in the future development [11].
3.1. Grid-Connected PV Model
The dynamic meteorological parametersof PV model are irradiance
( )
rr
I
and panel temperature
( )
T
, and the
simulation uses daily mode to realize the random characteristic.
Figure 2 shows a schematic diagram of the PV system device model.
W. P. Zhu et al.
253
Figure 2. Schematic diagram of PV model.
The active power, P, is a function of the
rr
I
, T, and rated power at the mpp, Pmpp at a selected temperature
and an irradiance of 1.0KW/m2. The model assumes the inverter is able to find the max power point (mpp) of
the panel quickly. Considering the losses of PV inverter, the model sets the efficiency factor for the inverter
(EFF). Define each temperature as well as its corresponding output power coefficient
T
F
curve, according to the
current temperature T to get output power coefficient
T
F
.
PV output power is calculated by formula (6).
mpp FFn rrT
PI PFE
=∗ ∗∗
(6)
Timing
rr
I
and T are selected to be the dynamic meteorological parameters of PV model on one day in the
second quarter in a region.
3.2. Model of Distribution Network
In this paper, the simulation uses the actual distribution network structure of a certain region.
According to the radial chain distribution network structure, each concentrated load along the feeder will be
seen as a node and be numbered. Considering the different types of transmission lines, which lead to the positive
and zero sequence resistance, positive and zero sequence reactance, positive and zero sequence capacitance of
lines and other parameters are different, the connection point of different types of transmission lines is also seen
as a node. The substation in the beginning is signed as N1. The simplified distribution network model is shown
in Figure 3.
Set the voltage of the beginning is 10.5kV, the parameters of three-phase lines and loads are the actual data of
a certain region. Assuming that the each phase impedance of lines and the each phase load of nodes are symme-
trical, the random power flow is calculated on the basis of this system with PV added in.
3.3. Scene of Grid-Connected PV
The typical scenes that PV accessed to the network are designed in order to obtain the reasonable planning ad-
vices. On the one hand, considering the internal factors of PV, output power of PV system mainly depends on its
capacity and power factor when the meteorological parameters arecertainty. On the other hand, considering the
relationship between PV and distribution network, output power now mainly depends on interconnected loca-
tions and dispersion degrees.
The typical scenes are designed and as shown below (Figure 4).
W. P. Zhu et al.
254
N1
N2
N8
N3
N7
N4
N6
N10
N9
N5
N15N13
N17
N12
N16
N11
N14 N19
N18
Figure 3. Simplified model of distribution network.
Typical scenes
Capacities
Power factors
Internal
factors
External
factors
0KW
700KW
1000KW
2000KW
500KW
1500KW
PF=-0.95
Interconnected
locations
Dispersion
degrees
N3
N19
N9
N8,N13,N19
PF
=1
PF=0.95
N16,N17,N19
N8,N9,N12
N2,N9,N19
N15
Figure 4. Typical scenes of PV accessed to the distribution network.
4. Results and Discussion
The distribution system is modeled and simulated by OpenDSS. The power flow of the distribution network and
the assessment indices are calculated under different PV access conditions. Then the paper analyzes the impacts
on static security of distribution network system with different grid-connected PV. The output power of PV sys-
tem is affected greatly by irradiance, so the power flow and network losses at 12 o’clock are taken to calculate
the normal operation ratio and network losses indices. The voltage fluctuation is a timing value.
4.1. Effects of PV Capacity on Distribution Network Security
Different capacities of PV are accessed to N19 in distribution network, set PF = 1.
1) Normal Operating Ratio
As you can see from Figure 5, the capacity of PV system has big influence on normal operation rate of dis-
tribution network. The normal operation rate decreases with increasing PV capacity, it can meet more load de-
mands. Then current becomes small and can reduce the line losses. But line L18 is connected with the PV access
W. P. Zhu et al.
255
point, its normal operation rate becomes larger with the capacity increases, so the capacity of PV should not be
too large to avoid the current of PV junction exceeds the normal allowable current.
2) Voltage Fluctuation Ratio
Figure 6 shows that the changes of voltage fluctuation rate are complex when PV system put into operation
and break off from the network. The voltage enhances greatly and thus the fluctuation ratio increases when PV
put into operation (around 7 a.m.). When PV out of operation (around 5 p.m.) and PV capacity is 1000 kw, the
voltage fluctuation ratio reaches a minimum due to the voltage support of PV system. If the capacity continues
to increase, the fluctuation ratio will deteriorate. At around 8 a.m. the system voltage varies greatly, the incre-
ment of capacity reduces the voltage obviously.
Comparing the data in Table 1, the capacity of PV is larger (no more than 1000 KW), the corresponding EV%
is smaller and the voltage fluctuation is improved. But when the capacity exceeds 1000 KW (about 35% of the
total power), EV% and the voltage fluctuation will be larger with the capacity increases. Considering the voltage
fluctuation of overall system, the capacity of PV should not more than the 35% of the total power.
3) Network losses
Figure 5. Normaloperating ratios under different PV capacities
Figure 6. Voltage fluctuation ratios under different PV capacities.
0
5
10
15
20
25
30
35
40
45
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
E/%
Lines
0KW
500KW
700KW
1000KW
1500KW
2000KW
0
0.05
0.1
0.15
0.2
0.25
0.3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
V%/%
Time
0KW
500KW
1000KW
1500KW
W. P. Zhu et al.
256
The grid-connected PV reduces the active power losses in a certain extent. The capacity is larger, the percen-
tage of power losses is smaller, and the value of M is greater, the network losses got better improvement (Table 2).
4.2. Effects of PV Locations on Distribution Network Security
PV systems are accessed to the distribution network at N3, N9, N15 and N19. Set each PV capacity is 700 KW
and PF = 1.
1) Normal Operating Ratio
From Figure 7, distribution network is in normal operating condition under different PV interconnected loca-
tions, and the closer to the end of distribution network, the lower current becomes.
2) Voltage Fluctuation Ratio
From Figure 8, interconnected location of PV has small influences on voltage fluctuation of distribution net-
work. Comparing the value of EV%, we will find that the closer to the end of the distribution network, the low-
er voltage fluctuation ratio is when PV capacity is appropriate (Table 3).
3) Network losses
As can be seen from Table 4, different interconnected locations have small effects on network losses. And the
closer to the end of network, the lower Ploss% is, and the value of M becomes higher at same time. It’s indicates
that network losses get a better improvement.
Table 1. Averages ofvoltage fluctuation ratiosunder different PV capacities.
KW 0 500 700 1000 1500 2000
E
V% 0.06659 0.06645 0.06641 0.06632 0.06766 0.06952
Table 2. Network lossesunder different PV capacities.
KW 0 500 700 1000 1500 2000
Ploss/kw 13 11.4 10.7 9.7 8.3 7.1
Ploss% 0.46% 0.399% 0.374% 0.339% 0.290% 0.248%
M 0 0.123 0.177 0.254 0.362 0.454
Figure 7. Normal operating ratios under different PV locations.
0
5
10
15
20
25
30
35
40
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
E/%
Li nes
N3
N9
N15
N19
W. P. Zhu et al.
257
Figure 8. Voltagefluctuation ratiosunder different locations.
Table 3. Average of voltage fluctuation ratiosunder different locations.
Location N3 N9 N15 N19
E
V% 0.06651 0.06644 0.06642 0.06641
Table 4. Network lossesunder different locations.
Location N = 3 N = 9 N = 15 N = 19
Ploss/kw 11.6 10.8 10.7 10.7
Ploss% 0.406% 0.378% 0.374% 0.374%
M 0.108 0.169 0.177 0.177
4.3. Effects of PV Dispersion Degrees on Distribution Network Security
Different combinations of PV are accessed to the distribution network, and each combination contains three PV
systems. Set each PV capacity is 250 KW and PF = 1. The combinations are show as below (Table 5).
The combination 1 of PV systems is evenly distributed in the distribution network. The combination 2 scat-
tered in the terminal of network. The combination 3 is concentrated in the middle location, and the combination
4 is concentrated in terminal.
1) Normal Operating Ratio
As you can see from Figure 9, the normal operation rate E of combination 4 islowest, the value of combina-
tion 3 is highest. This can be seen that the influences of PV dispersion degrees on distribution network is minor,
this mainly depends on the overall access location. When the distributed PV concentrated in the terminal of dis-
tribution network, the normal operation ratereaches the minimum, on the contrary, the E is the highest value
when PV systems concentrated in the middle position (Table 6).
2) Voltage Fluctuation Ratio
The Figure 10 can be seen, the dispersion degree of distributed PV also shows small effects on voltage fluc-
tuation of distribution network. Compare the average of voltage fluctuation ratio EV%, we can see that when PV
systems scattered in the distribution network, the voltage fluctuation rate is larger. On the contrary, the EV%
reaches the minimum when PV systems concentrated in the terminal position and the voltage fluctuation ratio
gets great improvement in this case.
0
0.05
0.1
0.15
0.2
0.25
0.3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
V%/%
Time
N3
N9
N15
N19
W. P. Zhu et al.
258
Table 5. Four combinations of distributed PV.
Combination PV1 PV2 PV3
1 N2 N9 N19
2 N8 N13 N19
3 N8 N9 N12
4 N16 N17 N19
Figure 9. Normal operating ratios under different dispersion degrees.
Figure 10. Voltage fluctuation ratios under different dispersion degrees.
0
5
10
15
20
25
30
35
40
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
E/%
Lines
combination 1
combination 2
combination 3
combination 4
0
0.05
0.1
0.15
0.2
0.25
0.3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
V%/%
Time
combination 1
combination 2
combination 3
combination 4
W. P. Zhu et al.
259
3) Network losses
As can be seen from Table 7, when distributed PV scatters in the distribution network, percentage of power
losses is highest and the value of M is lowest, that indicates the improvement of network losses is smallest.
Comparing the combination 2 with combination 3, we see that losses of combination 2 are lower. When PV sys-
tems concentrate in the end of network, percentage of power losses reaches the minimum and the value of M is
highest, the network losses have a best improvement in this case.
4.4. Effects of PV Power Factors on Distribution Network Security
Different power factors of PV systems with the capacity of 700 kW are accessed to the N19 separately. PF < 0
represents the PV system operates in the state that PV absorbs reactive power, PF > 0 represents the PV system
provides reactive power.
1) Normal Operating Ratio
Figure 11 shows that the power factors of PV have slight impacts on the normal operation ratio. The normal
operation ratio reaches the minimum when PV provides reactive power and equals 0.95. On the contrary, the
normal operation ratio reaches the maximum when PV absorbs reactive power and equals 0.95.
2) Voltage Fluctuation Ratio
Compare Figure 12 and EV%, we can see that the voltage fluctuation ratio is highest when PF < 0. When PF >
0, the voltage fluctuation ratio is lowest and has minimal impacts on the stable operation of the distribution net-
work in this case (Table 8).
3) Network losses
Table 6. Average of voltage fluctuation ratios under different dispersion degrees.
Combination 1 2 3 4
E
V% 0.066438 0.066408 0.066408 0.066394
Table 7. Network losses under different dispersion degrees.
Combination 1 2 3 4
Ploss/kw 11.0 10.6 10.7 10.5
Ploss% 0.383% 0.371% 0.374% 0.367%
M 0.154 0.185 0.177 0.192
Figure 11. Normal operating ratios under different power factors.
0
5
10
15
20
25
30
35
40
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
E/%
Lines
P F= -0.95
P F= 1
PF=0.95
W. P. Zhu et al.
260
Figure 12. Voltage Fluctuation ratios under different PV power factors.
Table 8. Average of voltage fluctuation ratios under different PV power factors.
PF –0.95 1 0.95
E
V% 0.06647 0.06641 0.06638
Table 9. Network losses under different power factors.
PF –0.95 1 0.95
Ploss/kw 11.0 10.7 10.4
Ploss% 0.383% 0.374% 0.364%
M 0.154 0.177 0.2
When PF < 0, the reactive power is absorbed, percentage of power loss reaches the maximum, and the value
of M is lowest, the network losses have the smallest improvement. On the contrary, when PF is running the con-
dition that provides the reactive power, Ploss% is lowest and the value of M is highest, the network losses have a
great improvement (Table 9).
5. Conclusions
1) On the premise of determining the interconnected location of PV, the PV permeability has a significant
impact on the normal operation ratio, fluctuation ratio and network losses of distribution network. When the ca-
pacity of grid-connected PV is larger(less than 35% of the total power), the normal operation ratio E of distribu-
tion system is smaller and the feeder current will not exceed the normal allowable current generally, and the
system can meet more load demands in this case. Meanwhile, the overall voltage fluctuation ratio will decrease
and the network losses will get a great improvement. However, if the PV capacity exceeds 35% of the total
power, not only is it easy to cause the system voltage exceeds the limit, but also the voltage fluctuation ratio and
network losses will increase. So the PV capacity should less than 35% of the total power.
2) When the capacity of grid-connected PV is appropriate, the interconnected location of PV has a slight im-
pact on the distribution network. The normal operation ratio E will be smaller when PV accesses to the end ter-
minal, meanwhile the voltage fluctuation ratio will getaimprovement and the network losses will decrease. Con-
sidering the risk of over voltage, the PV should be chose to access to the position that is near to the end of the
distribution network.
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
V%/ %
Time
P F=-0.95
P F=1
PF=0.95
W. P. Zhu et al.
261
3) When multiple PV systems are accessed to the distribution system, the dispersion degrees have a slight ef-
fect on the distribution network which mainly depends on whether the overall locations of PV systems are near
to the end of the system. When the distributed PV systems are accessed to the distribution network dispersedly,
the normal operation ratio and voltage fluctuation ratio is high, meanwhile, the network losses will get a small
improvement. On the contrary, the normal operation ratio is low when the distributed PV systems concentrate in
the end of distribution network, thus the network can meet more load demands and the voltage fluctuation ratio
will also decrease, the network losses have a great improvement.
4) Be sure that PV systems are accessed to the distribution network in an appropriate capacity and location,
the normal operation ratio E of distribution network system is low and the feeder current will not exceed the
normal allowable current generally when PF > 0 and PV provides reactive power. Meanwhile the voltage fluctu-
ation ratio decreases and the network losses of distribution network get a great improvement.
The paper only analyzes the static security of distribution system with the distributed PV. The research on
transient security will be discussed later.
References
[1] Xie, H.H. and Mao, J.L. (2011) Research on Security Indices and Method of Distribution Networks. Electric Power
Technology, 10, 39-41.
[2] Liu, R.X., Zhang, J.H. and Wu, D. (2011) Research on Static Security Index of Distribution Network Based on Risk
Theory. Power System Protection and Control, 39, 89-95.
[3] Xu, X.Y., Huang, Y.H., Liu, C. and Wang, W.S. (2010) Influence of Distributed Photovoltaic Generation on Voltage in
Distribution Network and Solution of Voltage beyond Limits. Power System Technology, 34, 140-146.
[4] Fan, Y.L., Zhao, B., Wang, Q.Y. and Cao, Y.J. (2012) Peak Capacity Calculation of Distributed Photovoltaic Source
with Constraint of Over-Voltage. Automation of Electric Power Systems, 36, 40-44.
[5] Dai, W.Z. (2011) Power System Security and Its Prevention. Electrical Engineering, 12, 85-89.
[6] Huang, X.K., Wang, H., Wang, Y.B. and Xu, H.H. (2014) Principle and Strategies of Voltage Rise Regulation for
Grid-Connected Photovoltaic Generation System at Point of Common Coupling. Automation of Electric Power Systems,
38, 112-117.
[7] He, H.Y., He, H.Q. and Li, X.S. (2014) Analysis on Effect of Distribution Photovoltaic Grid-Connection on Grid Net-
work Loss. Modern Electronics Technique, 37, 158-162.
[8] Shi, Z.G. (2010) Research of Impact of Grid-Connected Photovoltaic Power Generation System on Distribution Net-
work. Master’s Thesis, North China Electric Power University, Beijing.
[9] Xiao, Y.H., Yao, J.G. and Zhang, J. (2009) Analysis on Power Grid Safety Assessment System. Power System Tech-
nology, 33, 77-82.
[10] Wu, X.L. (2013) Impacts of Grid-Connected Photovoltaic Generation on Distribution System. Master’s Thesis, Hefei
University of Technology, Hefei.
[11] Nie, S. (2012) Analysis and Reconfiguration of Smart Distribution Network with Distributed Generation. Master’s
Thesis, Tianjin University, Tianjin.