Journal of Power and Energy Engineering, 2014, 2, 154-161
Published Online September 2014 in SciRes. http://www.scirp.org/journal/jpee
http://dx.doi.org/10.4236/jpee.2014.29022
How to cite this paper: Xia, C.J., Yang, Z.C., Men, K. and Zhao, Y. (2014) Analysis of Commutation Failure in Multi-Infeed
HVDC System under Different Load Models. Journal of Power and Energy Engineering, 2, 154-161.
http://dx.doi.org/10.4236/jpee.2014.29022
Analysis of Commutation Failure in
Multi-Infeed HVDC System under Different
Load Models
Chengjun Xia1, Zhongchao Yang1, Kun Men2, Yong Zhao2
1School of Electric Power, South China University of Technology, Guangzhou, China
2Electric Power Research Institute of CSG, China Southern Power Grid, Guangzhou, China
Email: y_zhongchao@163.com
Received June 2014
Abstract
HVDC technology has been widely used in modern power system. On one hand, HVDC has the ad-
vantages of economy, high efficiency and strong cont rollab ili ty. While on the other hand, it makes
the dynamic characteristics of the power system becoming more and more complex. That puts
forward a new challenge to system stability and raises new questions for power system simulation.
This paper focuses on the interaction between AC and DC systems, especially the problem of
commutation failure caused by AC system fault. Based on the data of China Southern Power Grid,
this paper calculates the fault regions that may cause commutation failure and calculates the sys-
tem critical clearance time under different load models, analyzes the impacts of different load
models on commutation failure and the stability of AC/DC hybrid system.
Keywords
AC/DC Hybrid System, Commutation Failure, Voltage of Converter Bus, Load Model, Power System
Simulation
1. Introduction
The HVDC transmission system has the advantages of high capacity, high efficiency and strong controllability,
and it had been widely used in power system [1]. As the development of power electronics and control technol-
ogy, the HVDC will have a broad application in the future. However, the HVDC also puts forward some new
challenges to system operation, the AC/DC in ter action has become an emphasis for researchers [2] [3].
In all sorts of problems exposed in AC/DC hybrid system, commutation failure caused by AC system fault is
the most common one. Commutation failure can lead to DC voltage sag, DC current swell, DC power decrease,
reduction of converter valve service life, DC magnetic biasing of converter transformer and overvoltage of
“weakreceiving end system. For multi-infeed HVDC system, the electrical distance between each inverter sta-
tion is short, the AC/DC interaction features are more complex, commutation failure occurs in one inverter sta-
tion may lead to commutation failure of nearby inverter stations at the same time. In severe cases, that may lead
to DC power interruption, which will be a serious threat to the stability of AC/DC hybrid system [4]-[6].
C. J. Xia et al.
155
Research on commutation failure is significant for understanding the operation features of AC/DC hybrid
system, improving the system operating condition and enhancing the system stability. Researchers had carried
out large amount of research work. Reference [7] [8] focused on the extinction angle γ, analyzed the factors of
commutation failure in detail. Refer ence [9] pointed out that the voltage sag of converter bus caused by AC sys-
tem fault is the main cause of commutation failure. In [10] and [11], a new indexCFII (Commutation Failure
Immunity Index) was proposed to evaluate the converters resistance to commutation failure cause by AC sys-
tem fault. In [12], a criterion of commutation failure was proposed based on a great deal of simulation study.
However, the previous research paid less attention to the load model. In fact, it can be found from the simulation
result that, the occurrence of HVDC commutation failure has a close relationship with load model. This paper
points out that the mechanical inertia of the motor load will affect the occurrence of commutation failure. Simu-
lation is carried out to verify the viewpoint proposed in this paper.
2. Mechanism and Factors of Commutation Failure
The occurrence of commutation failure caused by AC system fault is related to the strength of receiving end
system. The strongerthe receiving end is, the weaker the AC/D C influence each other and the less probable
the commutation failure will occur. The strength of receiving end system can be evaluated from two aspects.
On one hand, the strength can be evaluated by the indicator SCR (Short Circuit Ratio), which is defined as
follow
S
SCR
dN
P
=
(1)
where S is the thr ee-phase short-circuit capacity of receiving end system when the voltage of converter bus is at
1 p.u. PdN is the rated power of HVDC. In [13] the strength of AC system was divided into three levels according
to SCR: high (SCR > 3), low (2 SCR 3), very low (SCR < 2).
On the other hand, the system strength can be evaluated by the mechanical inertia. If the mechanical inertia is
large enough, the potential of generators will maintain when fault occurs, that will be beneficial for voltage re-
covery and preventing system from collapsing. It can be said that the larger the mechanical inertia is the stronger
the receiving end system will be. Generator rotors are the main source of mechanical inertia, but it should be
pointed out that, except from generators, the motor load can also provide mechanical inertia.
The thyristors used in HVDC system is a kind of half controlled component, the commutation process needs a
certain time for internal carrier recombination and blocking ability restoring. The time of carrier recombination
process can be evaluated by extinction angle γ. γ is important for the operation of inverter, if the operating γ <
γmin, the internal carrier of thyristor s will not have enough time to recombine and commutation failure will occur.
Extinction angle γ can be described as follow [14]
2
arccos(cos )
dc
kI X
E
γβ
= +
(2)
where E is the voltage of converter bus, k is the ratio of converter transformer, β is the advance trigger angle, Id
is the DC current, Xc is the commutation reactor. For a certain HVDC, its commutation reactor could be consid-
ered as a constant. When fault occurs in receiving end AC system, the DC controllers and the tap changers can-
not response immediately. So the β and k remain unchanged at the instance of fault. The increase of DC current
or the decline of converter bus voltage will lead to the decrease of γ. If γ decreases below γmin, commutation fail-
ure will occur. The influence of converter bus voltage on commutation failure is this paper mainly concerns
about.
For multi-infeed HVDC system, when short circuit fault occurs in the receivin g end, the voltage of converter
bus will decline, and that may results in commutation failure in more than one inverter stations at the same time.
In power system, there are many kinds of load. Different load models will have different impact on the decline
of voltage, thus influence the occurance of commutation failure.
3. Impact of Different Load Models on Voltage Decline
3.1. Static Load Model
The static load model can reflect the change of active and reactive load as the frequency and voltage change
C. J. Xia et al.
156
slowly [15]. ZIP model is a kind of static load, and it is most widely used in simulation. The ZIP load consists of
three components: constant impedance load, constant current load and constant power lo ad . It can be described
as follow
2
000
2
000
[()() ](1)
[()() ](1)
L ZIPPf
L ZIPQf
VV
PPPPPf L
VV
VV
Q QQQQfL
VV
=+++∆ ⋅
=+++∆ ⋅
(3)
where PZ, QZ are the percentage of constant impedance active and reactive load; PI, QI are the percentage of
constant current active and reactive load; PP, QP are the percentage of constant power active and reactive load,
and satisfy PZ + PI + PP = QZ + QI + QP = 1. P0, Q0, V0 are activ e load, reactive load and voltage of the system
under steady state. Δf is the deviation of the actual value and steady-state value of system frequency.
When fault occurs in AC system, the voltage will decline immediately, and the frequency remains unchanged
at the instance of fault. It can be seen from Equation (3) that the constant impedance load is proportional to the
square of voltage, so its reactive power consumption will drop rapidly as the voltage decline after fault, which is
beneficial for preventing the voltage from declining further. The constant power load is irrelevant to voltage. Its
reactive power consumption will not change as the voltage decline and it makes no contribution to preventing
voltage decline [16]. The constant current load is proportional to first power of the voltag e . Its contribution to
preventing voltage sag is between constant impedance load and constant power load.
3.2. Dynamic Load Model
In comparison with static load, the dynamic load can reflect the change of active and reactive load relative to the
fast change of frequency and voltage. There are many kinds of dynamic load in power system, and the motor
load is the most common one. The simple equivalent circuit of motor is showed in Figure 1. Where
U
is the
input voltage,
I
is the rotor current, Xm is the excitation reactance, Xr is the rotor leakage reactance, Rr is the
rotor resistance, s is the slip. The reactive power consumption of the motor load can be described as follow [17]
(4)
where
2
/
mm
QUX=
is the exciting power of the motor,
2
rr
Q IX=
is the reactive power consumption of ro-
tor leakage reactance. Variable resistance Rr/s in Figure 1 is equivalent to the mechanical load of the motor, and
the mechanical load P can be described as follow
2/
r
PIR s=
(5)
From Equation (4) we can see that the exciting power Qm is proportional to the square of voltage, so it will
reduce significantly as voltage sags after fault. Because of the inertia of motor rotor, the speed of motor cannot
change suddenly, so the slip also remains unchanged at the instance of fault. Assume that the mechanical load of
the motor also remains the same. We can see from Equation (5) that the rotor current will mainta in the same,
thus the reactive power consumption of rotor leakage reactance will not increase. That means the motor load, as
revolving equipment, can remain its speed unchanged at the instance of fault because of its inertia, and reduce
its exciting power significantly without increasing the reactive power consumption of rotor leakage reactance at
the same time. Compared with ZIP load, the motor load is better in enhancing the system voltage support.
However, in the duration of disturbance, as the electromagnetic torque of motor is proportional to the square
of the input voltage U, the decline of voltage will lead to the reduction of electromagnetic torque. If the me-
chanical torque of motor load remains unchanged, the speed will drop continuously until the rotor is blocked. In
X
r
X
m
R
r
/s
U
I
Figure 1. The equivalent circuit of induction motor.
C. J. Xia et al.
157
this process, the slip will increase and approximate to 1. From Equation (5), the current I will increase, so do the
reactive power consumption of rotor leakage reactance, and that is not good for voltage recovering [18]-[20].
4. Simulation
4.1. Criterion of Commutation Failure
The paper adopts the criterion proposed in [12]: when using BPA to do the simulation, set three-phase fault in
different position of the system, if the three-phase voltage of converter bus decline below 90% the value before
fault, commutation failure is consider to occur.
4.2. Simulation of Commutation Failure
The simulation of this paper is based on the data of China Southern Power Grid (CSG) which is the largest and
most complex AC/DC hybrid power system. There will be totally 7 HVDCs in 2014: Tian-guang, Yun-guang,
Xin-an, Gao-zhao, Jiangcheng, Nuozhadu and Xiluodu. All these HVDCs terminate at Guangdong. A simple
diagram of HVDCs in CSG is show in Figure 2.
The load models of simulation include ZIP load, 40% motor load and 60% constant impedance load in paral-
lel, 50% motor load and 50% constant impedance load in parallel, 60% motor load and 40% constant impedance
load in parallel. The ZIP load is consisted of 30% of constant impedance load, 40% of constant current load and
30% of constant power load. The parameters of motor load are showed in Table 1.
Three-phase fault is set to occur at 500 kV nodes in Guangdong. Calculate the bus voltage of inverter stations
and use the criterio n proposed in [12] to judge the occurrence of commutation failure. A simulation result is
showed in Table 2. In this case, the fault is set at 500 kV substation Pengcheng.
From Table 2 we can see that when the load model is motor and constant impedance in parallel, the decline of
bus voltage reduce significantly at the instance of fault. As the percentage of motor load increase, decline of bus
voltage reduce further.
To make the simulation result more intuitive, Figures 3-6 show the fault region that may resul t in commuta-
tion failure occur in more than three inverters.
Figure 2. Simple diagram of HVDCs in CSG.
Table 1. The parameter of induction motor model.
Parameter Value
Inertia time constant (s) 2
Load rate 0.51
Stator resistance (p.u.) 0
Stator reactance (p.u.) 0.18
excitation reactance (p.u.) 3.5
Rotor resistance (p.u.) 0.02
Rotor reactance (p.u.) 0.12
Constant A of mechanical torque equation 0.887 5
Constant B of mechanical torque equation 0.04
C. J. Xia et al.
158
Table 2. Voltage sag and commutation failure when fault occurs at Pengcheng.
ZIP load 40% motor load 50% motor load 60% motor load
Xin-an Percentage of the voltage before fault (%) 4.37 6.54 6.87 7 . 15
Commutation failure occurance Yes Yes Yes Yes
Gao-zhao Percentage of the voltage before fault (%) 92.78 97.93 98.22 98.44
Commutation failure occurance No No No No
Tian-guang Percentage of the voltage before fault (%) 86.52 96.10 96.72 97.17
Commutation failure occurance Yes No No No
Jiangcheng Percentage of the voltage before fault (%) 79.08 88.28 89.18 89.90
Commutation failure occurance Yes Yes Yes Yes
Yun-g ua ng Percentage of the voltage before fault (%) 81.65 90.89 91.68 92.30
Commutation failure occurance Yes No No No
Nuozhadu Percentage of the voltage before fault (%) 95.68 98.90 99.07 99.18
Commutation failure occurance No No No No
Xiluodu Percentage of the voltage before fault (%) 85.97 94.94 95.52 95.96
Commutation failure occurance Yes No No No
Figure 3. Fault region under ZIP load.
Figure 4. Fault region under 40% of motor load.
C. J. Xia et al.
159
Figure 5. Fault region under 50% of motor load.
Figure 6. Fault region under 60% of motor load.
From the four figures above we can see that when using motor load in simulation, the fault region decrease
significantly than using ZIP load. As the proportion of motor load increase, the fault region decrease further.
That demonstrates the viewpoint of Section 3.2: the motor load can provide inertia to the system, so it is better
than ZIP load in supporting the system voltage and reducing the possibility of commutation failure.
Different HVDC show different sensitivity to AC system fault. Table 3 lists the number of fault node that
may lead to commutation failu re at different inverter. The number of fault nodes can, to a certain extent, show
the HVDCssensitivity to AC system fault.
From Table 3 we can see that Xiluodu HVDC has the highest sensitivity to AC system fault, while Xin-an
HVDC is relatively lower. Ove rall, the sensitivity of each HVDC decreases as the percentage of motor load in-
crease.
4.3. Simulation of System Transient Stability
Based on the data of CSG, this paper calculates the system critical clearance time under two load models: ZIP
load and 40% motor load 60% constant resistance load in parallel. The result is showed in Table 4.
From Table 4 we can see that compared with ZIP load, the motor load will reduce the system critical clear-
ance time. That demonstrates the viewpoint of Section 3.2: the motor load will consume more reactive power in
the duration of fault, which is bad for voltage recovering and do harm to the system transient stability.
5. Conclusions
This paper analyzes the Mechanism and factors of commutation failure, studies the load modelsimpact on com-
C. J. Xia et al.
160
Table 3. Comparision of the sensitivity of each HVDC to AC system fault.
HVDC ZIP Load 40% Motor load
50% Motor load
60% Motor load
Xin-an 41 24 21 18
Gao-zhao 58 32 29 27
Tian-guang 69 21 19 18
Jiangcheng 59 34 30 28
Yung-guang 64 24 23 21
Nuozhadu 49 29 29 29
Xiluodu 69 27 27 27
Table 4. Comparision of system critical clearance time under different load
models.
Fault Node System Critical Clearance Time (s)
ZIP Load 40% Motor Load
Suidong 0.34 0.26
Zhaoqing 0.66 0.54
Baoan 0.28 0.22
Beijiao 0.34 0.28
Echeng >1.5 >1.5
mutation failure based on simulation. The conclusions of this paper are:
1) As the motor load can provide inertia to the system at the instance of fault, it is better than ZIP load in pre-
venting voltage from declining, reducing the possibility of commutation failure and reducing the fault region
that may lead to commutation failure occur in more than one inverters.
2) In the duration of fault, the motor load will enlarge the lack of reactive power and damage the system tran-
sient stability.
The conclusion of this paper would be useful in simulation and engineering applications.
References
[1] Zhao, W.J. (2004) Engineering Technology of HVDC Transmission Sy st e m. China Electric Power Press, Beijing, 125.
[2] Yang, W.D., Xu, Z. and Han, Z.X. (2000) Special Issues and Suggestions on Multi-Infeed AC/DC Power Systems.
Power System Technology, 24, 13-17.
[3] Xu, Z. (1998) AC/DC and DC/DC Interactions of Multiple HVDC Links Terminating in the Same AC System. Power
System Technology, 22, 16-19.
[4] Thio C. V., Da vi se J. B. and Kent K. L. (1996) Commutation Failures in HVDC Transmission Syst ems. IEEE Trans-
actions on Power Delivery, 11, 946-957. http://dx.doi.org/10.1109/61.489356
[5] Lin, L.X., Zha ng , Y., Zhong, Q. and Zong, X.H. (2006) A Survey on Commutation Failures in Multi-infeed HVDC
Transmission Systems. Power System Technology, 30, 40-46.
[6] Chen, S.Y., Li, X.N., Yu, J., Li, T., Lv, P.F. and Yin, Y.H. (2005) A Method Based on the Sin-Cos Components De-
tection Mitigates Commutation Failure in HVDC. Proceedings of the CSEE, 25, 1-6.
[7] Ou, K.J., Ren, Z. and Jing, Y. (2003) Research on Commutation Failure in HVDC Transmission System Part 1: Com-
mutation Failure Factors Analysis. Electric Power Automation Equipment, 23, 5-8.
[8] Hao, Y.D. and Ni, R.B. (2006) Analysis on Influence Factors of Commutation Failure in HVDC. High Voltage Engi-
neering, 32, 38-41.
[9] Hong, C. (2011) Simulation Analysis on the Commutation Failure and Power Recovery Characteristic of an Actual DC
Transmission System. Southern Power System Technology, 5, 1-7.
[10] Rahimi, E., Gole, A.M., Davies, J.B., Fernando, I.T. and Kent, K.L. (2006) Commutation Failure in Single- and
Multi-infeed HVDC Systems. The 8th IEE International Conference, London, 182-186.
[11] Rahimi, E., Gole, A.M., Davies, J.B., Fernando, I.T. and Ke nt, K.L. (2011) Commutation Failure Analysis in Multi-
C. J. Xia et al.
161
Infeed HVDC Syste ms. IEEE Transactions on Power Delivery, 26, 378-384.
http://dx.doi.org/10.1109/TPWRD.2010.2081692
[12] Power Research Institute of CSG (2012) Research on AC/DC Interaction and Solution in China Southern Power Grid
Receiving End System. Research Report of CSG.
[13] (1997) Guide for Planning DC Links Terminating at AC Locations Having Low Short Circuit Capacities. IEEE Std
1204, 5.
[14] Li, X.Y. (1998) Operation and Control of HVDC Transmission Syst e m. Science Press, Beijing, 2-4.
[15] Kundur, P. (1994) Power System Stability and Control. McGraw-Hill, New York.
[16] Wang, Z.F., Xue, Y.S. and Yang, W.D. (2006) Influences of Load Models on DC/AC System Stability. Automation of
Electric Power Systems, 30, 13-16.
[17] He, Y.Z. and Wen, Z.Y. (2001) Power System Analysis. Huazhong University of Science and Technology Press, Wu-
han, 77-78.
[18] Xu, Z.X. (2006) Dynamic Load Modeling for Transient Stability Study of Regional Interconnected Power Syste m .
Electric Power, 38, 15-19.
[19] Zhang, P.F., Luo, C.L., Meng, Y.J. (2006) Impact of Dynamic Electric Load Model Proportion on Power System Sta-
bility. Relay, 34, 24-26.
[20] Liao, M.C., Cai, G.L. and Zhang, Y.J. (2009) Transient Voltage Stability of Received Power Grid in AC/DC Hybrid
Power Systems. Power System Protection and Control, 37, 5-8.