Journal of Power and Energy Engineering, 2014, 2, 554-563 Published Online April 2014 in SciRes. http://www.scirp.org/journal/jpee http://dx.doi.org/10.4236/jpee.2014.24075 How to cite this paper: Chen, L.K., Lai, W.Q., Wang, J., Jiang, G.Y., Zhou, Y., Chen, Y., L iu, H.B., Qin, Z.Y., Ke, L., Wang, L. and Shen, Y. (2014) Study on Surface Electric Field Simulation of High Voltage Transmission Line Assembly. Journal of Power and Energy Engineering, 2, 554-563. http://dx.doi.org/10.4236/jpee.20 14.24075 Study on Surface Electric Field Simulation of High Voltage Transmission Line Assembly Liankai Chen1, We nqing Lai1, Jun Wang 2, Guo y i Jiang 1, Yan Zhou1, Yong Chen2, Haibo Liu1, Zhaoyu Qin2, Lei Ke2, Lei Wang2, Yang Shen2 1East Inner Mongolia Electric Power Company Limited, Inner Mongolia, Hohhot, China 2Wuhan NARI Limited Liability Company of State Grid Electric Power Research Institute, Wuhan, China Email: chenliankai@md.sgcc.com.cn Received September 2013 Abstract For the stud ies in the field of high voltage power transmission, this paper has adopted the method of finite element node potential, and put forward two kinds of high pressure sensor-fixture mod- eling scheme for the sensor-fixture of the high voltage side, the simulation analysis shows that the sensor-fixture surface should be smooth, and should not appear the conclusion of edges and cor- ners. While through establishing the four clamps assembly optimized model, and simulates the strain gages, fixtures and conductor surface field strength and electric field distribution in the model as a whole in turn, this paper Finally got the optimal size of fixture structure and assembly of each part reasonable location layout. Keywords High Voltage Assembly; Finite Element Method; Simulation Calculation; Electric Field Distribution 1. Introduction Transmission line is the material basis for the development of electric power industry. The transmission grid fa- cilities are burdened with the task of transmission and distribution of electrical energy, the reliability and oper- ating conditions of which directly determine the stability and security of the entire system, but also determine the power quality and reliability of supply. Currently, with the difficult inspection and heavy maintenance workload, if the problems on the transmission line cannot be promptly found and solved, it will affect the coun- try's production and residents’ life, which has become an imperative social problem that ensures the safety and smooth flow of the power “lifeline” [1]. With the increasing of the grid capacity and transmission voltage rating, it’s becoming increasingly important that the on-line monitoring of the performance of the high voltage power transmission equipment in operating [2]. 2. Calculation Principl e 2.1. Finite Element Analysis of Electrostatic Field At present, the electromagnetic field numerical calculation method commonly used at home and abroad is the
L. K. Chen et al. charge simulation method of finite element method, boundary element method, finite difference method, and a variety of methods of coupling or mixed application method etc. [3]. Calculation of the model in this study is composed of a variety of media, and the model is more complex, which can be calculated by finite element method Finite element method based on variation principles, com- bined with the Difference method and developed a numerical method. Electrostatic field potential energy can be expressed as a function and its derivative pending integral of the integration region (or solving the field), in accordance with the differential method of discrete method, it is di- vided into finite sub-regions (called cells). And then use these discrete units, the electrostatic field energy be ap- proximated by a finite number of nodes in the potential of the function [4]. Thus, the electrostatic field energy demand is reduced to the problem of extreme multi-function extremum problem, which usually boils down to a set of multivariate linear algebraic equations finite element equation. Finally, the specific characteristics of equ- ations, using appropriate algebraic methods, and seek each node potential, to achieve a discrete solution of vari- ation problems. In the electrostatic field, generally solving potential of is a direct object. In isotropic, linear, homogeneous medium, the potential to meet the Poisson equation or the Laplace equation: (1) Or (2) whe re , is free charge density, is the dielectric constant. Based on the principle of least action electrostatic field, in the medium a fixed charge system, the surface charge distribution of the electric field tends to always make synthesis with minimal electrostatic energy [5]. The entire field for a given potential values on the boundary of the first class of boundary value problems, energy integral expression is: 2 2 min 2 eD W dxdydz xy εϕϕ ρϕ ∂∂ = +−= ∂∂ ∫∫ (3) Finite element method is a continuous field via split into a finite number of discrete units, in two-dimensional field problems commonly used to split triangular and quadrilateral elements, within each cell of the potential function approximated by polynomial interpolation. After the split, the secondary functional can be expressed as the sum of all the cells energy function: (4) In the formula, represents the element of the corresponding triangular energy integral, which is a unit of energy integration [6]: 22 F( )F()min 2 ee e ee D dxdy xy εϕ ϕ ϕϕ ∂∂ ≈= += ∂∂ ∫∫ (5) While: (6) Then: 2 2 1 dd dd 22 e eqe ii i DD N xy xy xx εϕε ϕ = ∂ ∂= ∂∂ ∑ ∫∫ ∫∫ (7) If is independent of x, then:
L. K. Chen et al. 2 T dd 2 ee ee x D xy x εϕ ϕϕ ∂= ∂ ∫∫ K (8) Of which: (9) (10) is the split region enclosed area. Similarly, if has nothing to do with y, then: (11) (12) Therefore: (13) All sub-regions combined simultaneous equations, we obtain: (14) where and K is the set of simultaneous equations after all the variables and coefficient matrix. So the problem is discretized into functional multivariate quadratic function extremum problem: (15) By the function extreme value theory, we have: (16) The formula is: (17) The above equation is the finite element equations, which can solve the equation by using the boundary con- ditions; and you can get the desired approximate solution. In summary, the finite element method calculation steps are as follows: 1) Clear field range, the field split into a finite element (two-dimensional field can be trilateral or quadrilateral 11 121 21 222 12 2 q q e x q qqq N NN NNN xx xxxx N NN NNN Sxx xxxx N NNN NN xx xxxx ε ∂ ∂∂ ∂∂∂ ∂∂ ∂∂∂∂ ∂ ∂∂ ∂∂∂ =∂∂ ∂∂∂∂ ∂ ∂∂∂ ∂∂ ∂∂ ∂∂∂∂ K 2 2 1 () e eqee ee iiy i N yy ϕϕ ϕϕ = ∂ ∂= = ∂∂ ∑ Τ K 11 121 21 222 12 2 q q e y q qqq N NN NNN yy yyyy N NN NNN Syy yyyy N NNN NN yy yyyy ε ∂ ∂∂ ∂∂∂ ∂∂ ∂∂∂∂ ∂ ∂∂ ∂∂∂ =∂∂ ∂∂∂∂ ∂ ∂∂∂ ∂∂ ∂∂ ∂∂∂∂ K F( )() ee eee e xy ϕϕ ϕ = + Τ KK
L. K. Chen et al. base unit, three-dimensional field available tetrahedral or hexahedral basic unit); 2) Electric energy calculation unit elements of the coefficient matrix; 3) Calculate the total electric energy coefficient matrix elements; 4) Finite element equations are listed; 5) Solving the finite element equations, find the node potential; 6) Potential can be calculated based on each node’s remaining amount of the electric field. 2.2. ANSYS Software in the Application of the Electrostatic Field Calculation ANSYS is the financial structure, fluid, electric, magnetic, acoustic analysis in one large general-purpose finite element analysis software. Its electromagnetic field analysis includes several modules: low frequency, high fre- quency, high frequency TV size (MOM), cable bundle electromagnetic compatibility (EMC) and signal integrity (SI), PCB’s and other EMC and SI [7]. It works with most CAD software interface, data sharing and exchange, such as Pro/Engineer, AutoCAD, Solid works, etc. ANSYS analysis process consists of three main steps: pre-treatment (create or read into the finite element model, defining material properties, mesh); loading and solving (applied load and set constraints solving); post-treatment (see Analysis a result, the check result is correct) [8]. Among them, the pre-treatment of the mechanical structure of the system is mainly made-up of nodes and elements into the mix into a finite element model of the various parts of its defined element type, material prop- erties and real constants, then meshing, finite element model to obtain the unknown nodes and elements. Load- ing and Solution mainly defined properly, the correct load system components in order to understand the struc- ture after the reaction by the external load, load on the finite element model, then select the appropriate direct solver and iterative solver for solving computing nodes [9]. The subsequent processing is mainly analysis node inspection and unit results. 3. Calculation Models and Parameters Established 3.1. Research Contents In order to effectively avoid the transmission line conductor aeolian vibration caused by the wire off shares ac- cidents, it requires real-time monitoring of wire in the breeze under the vibration information, so need to install the wire strain measuring device measuring wire strain. Strain gauge the middle part of the metal, composite material with metal wire ends, fixture and fixed with strain gage. Strain gauge on the wire installation diagram as shown in Figure 1. Different structure of the metal fixture assembly surface field strength will produce dif- ferent effects, so the need for fixture structure modeling of different options to select the optimal metal clamp structure to reduce vibration and point discharge breeze on high-voltage transmission wires resulting damage. n this study, a high-pressure side sensor fixture design two programs, In order to verify the merits of two kind of fixture, respectively, finite element analysis of the phenomenon of charge concentration of two kinds of fix- ture scheme. The following is the detailed modeling program. Figure 1. Strain gauge assembly simulation diagram.
L. K. Chen et al. 3.2. Sensor Fixture Modeling The surface of the clamp tip scheme I will have the electric field concentration, and easily lead to burn out the wire tip discharge, while the scheme II uses the methods to avoid the tip, the fixture body with circular arc de- sign, the design of bolt connection parts of sinking, completely hidden in the fixture screw bolt, Compact struc- ture design of high voltage side as shown in Figure 2. Since two briquetting symmetrical structure and coupling docking, we are concerned about the charge distri- bution is mainly concentrated in the outer surface of the arc. To save modeling time is taken in the right briquet- ting COMSOL modeling and analysis, shown in Figure 3. Similarly, removal of the air domain compact struc- ture only concerned with compact contour of the air within the inner boundary of the electric field distribution. The simulation parameters are shown in Table 1. Figure 2. Compact structure design of high voltage. Figure 3. The compacts parcels by air domain.
L. K. Chen et al. Table 1. Scheme of B simulation parameter list. simulation parameter Parameter values Geometric parameters With length 80 mm, width 120 mm, 60 mm high air field surrounded fixture. Air domain and the pressing block center symmetry. Material parameters air Meshing Using user-controlled mesh, the largest unit length 2 mm, the smallest unit of length 1 mm, cell growth rate of 1.3. Finally mesh degrees of freedom 1,854,100. Boundary Conditions Fixture inner contour of the air domain boundary, surface potential 220 kV, air domain boundaries are deemed to be grounded. 4. Results and Analysis 4.1. Analysis of Sensor Modeling Scheme I of Fixture Results A sensor jig modeling scheme potential distribution of the simulation results shown in Figure 4, we can clearly see the outline edge clamps outwardly from the 220 kV to zero potential (ground) of the uniform field in the ambient air. The electric field distribution simulation results shows that the electric field concentration at the tip of the metal clamp surface corner. The surface potential of 220 kV case, the tip surface of the field about 5.32 × 107 v/m, and in the circular surface is uniform electric field distribution. So, in order to avoid the discharge temper- ature and humidity in the extreme case, fixture surface should be smooth. 4.2. Analysis of Sensor Modeling Scheme II of Fixture Results The results of simulation of air field potential distribution scheme of II as shown in Figure 5, potential along the air domain boundary from 220 kV to 0 steady decline, and the scheme of simulation results similar to I. The electric field distribution simulation results as shown in Figure 8, the electric field intensity around the right arc is about 1.81e7 - 1.87e7 V/m. It is much lower than the electric field of a rectangular boundary scheme of fixture design focus on the value, and the uniform electric field distribution, no surge spikes. Comparison of the simulation results of plan I and II, the electric field concentration at the tip of the metal clamp surface corner. The surface potential of 220 kV case, the tip surface of the electric field is about 5.32 × 107v / m, and in the circular surface is uniform electric field distribution. Peak electric arc chamfer is about 2.18e7 V/m - 2.36e7 V/m, and the rectangular clamp tip electric field peak compared to 5.32e7 V/m is reduced by about 50%, and the boundary of uniform electric field distribution. Arc pressing block is not easy to generate point discharge, optimization design. In order to avoid the discharge temperature and humidity in the extreme case, fixture surface should be smooth [10]. The optimization scheme is to use arc chamfering, and as far as possible to ensure that the surface finish. Give extended application, low end fixture, especially from the wire clamp close, in order to avoid the tip electric caused by induction, the edges and corners also need passivation [11]. 4.3. Results and Analysis of the Electric Field Distribution Simulation Model Assembly This study is based 220 kV transmission line of the finite element model was established by the four kinds of mode, Model A is the original model, model B is the only changes bolt model, model C in the second model, based on the composite metal and the sensor connection portion is placed jig hole, model D is changed rounded 0.8 mm bolt hole wall model, outsourcing air cylinder modeled by a radius of 100 m. Using ANSYS software based on a section of the model diagram of four models for the combination of data modeling. Model A is the original model; model B is changed bolt model; C model based on B model, the sen- sor metal and composite joints on the fixture hole; model of D is modified bolt hole wall fillet 0.8 mm model; the overall distribution of the electric field then the simulation of the four types of models, the whole field dis- tribution results are shown in Figures 6-9. From this point of view of the whole electric field distribution, models A and the electric field under the other three models are quite different, model B, model C and model D is close to. The maximum field intensity model A appeared on the ends of the bolts is 64.19 kV/cm, maximum field strength, model B, model C and model D is
L. K. Chen et al. Figure 4. Distribution of the air domain potential surrounding the fixture in scheme I. Figure 5. Distribution of the air domain potential surrounding the fixture scheme in B. appeared in the top corner of fixture, the maximum electric field strength model for B 28.14 kV/cm, the maxi- mum field strength model for C 28.16 kV/cm, the maximum field strength model of D is 28.26 kV/cm, the maximum electric field strength of three kinds of model are very small. In order to compare the difference between different models of the maximum field intensity, listed in Table 2 field in different parts of the different model maximum. As can be seen from the Table 2, the potential of the composite section in both ends of strain gauge uneven
L. K. Chen et al. Figure 6. Model A whole field distribution. Figure 7. Model B whole field distribution. Table 2. Different models of different parts of the maximum value. Model A Model B Model C Model D The maximum electric field value (kV/cm ) 6 4.19 28. 14 28.16 28.26 Conductor surface field maximum (kV/cm) 15.77 15.74 15.77 15.82 Clamp the maximum surface electric field (kV/cm) 27.64 28.14 28.06 2 8.26 The maximum strain gage surface electric field (kV/cm) 21.13 21.75 16.65 15.94
L. K. Chen et al. Figure 8. Model C whole field distribution. Figure 9. Model D whole field distribution. distributed in the four models. The potential is highest at the part connect with the metal, and lowest at both ends. The overall integral maximum field value in model one was significantly higher than the other three models. At the same time, the maximum field strength value of strain gauges in model one and model two was greater than the other two models. Comprehensive comparison of the four models, proposed to shorten the clamp bolt to place the end portion inside the clamp in order to avoid excessive field strength appears. The fillet radius of clamp portion can be appropriately enlarged to reduce the surface field strength [12].
L. K. Chen et al. 5. Summary Through the simulation and analysis and comparison of the two modeling programs of sensor fixture, that the electric field distributed more concentrated at the corner of the tip of the metal clamp’s surface, while it’s more even at the arc surface. The surfaces of metal clamps should be as smooth as possible, do not appear at the an- gular [13], the optimal approach is to use curved chamfer, which can effectively avoid the discharge at the tips under the extreme temperature conditions. In the design of the model assembled, place the joints which con- nected with metal and composite material inside the clamps, to prevent the field strength is too large on the sur- face of the strain gauge. And the metal fixture can reduce its surface field strength by properly increasing the fillet radius, making the design of model assembly optimized. References [1] Wang , J.-Y., F ang, C.-E., Dai, Y.-S., Li, W. an d Hou, X.-Y. (2007) Electric Field Calculation and Optimal Design of 35 kV Contactor Box. High Voltage Engineering, 33, 63-65. [2] Zhang, Y.-J., Li, X., Li u , H.-B. and Sun, H.-H. (2012) Calculation and Optimization of Electric Field for 220 kV Composite Hollow Insulators. North China Electric Power, 6, 16-19. [3] Yang, Y. (2013) Calculation and Analysis of Total Electric Field at Ground Level beneath 800 kV DC Transmission Lines With Out-of-Operational Negative Pole Line. Power System Technology, 37, 1531-1535. [4] Huang, D.C., Ru an, J.J., Ch e n, Y., H uo, F., Yu, S.F. and Liu , S.B. (2008) Study on the Voltage and Electric Field Dis- tribution along Composite Insulator of 1000 kV AC Transmission Li n e. Proceedings of the CSEE, 52-57. [5] Li, Y. and Zhu , L.-X. (2013) Main Insulation Electric Field Calculation and Analysis Software for Power Transformer. Transformer, 50, 52 -56 . [6] Jiang, X. an d Wang, Z.Y. (2004) Calculation and Analysis for the Electric Field of Composite High Voltage Bushing. High Voltage Engineering, 30, 17-21. [7] Lin, X., Cai, Q., Xu, J.-Y. and Li, S. (2011) Large Scale of Electric Field Calculation of 1100 kV Disconnector Based on Domain Decomposition Method. High Voltage Apparatus, 47, 1-6. [8] Zhou , X.X . , Lu, T.B., Cui, X., Zh en , Y.Z an d Lu o, Z.N. (2011) A Hybrid Method for the Simulation of Ion Flow Field of HVDC Transmission Lines Based on Finite Element Method and Finite Volume Method. Proceedings of the CSEE, 31, 127-133. [9] Huang, D.-C., R uan , J.-J. and Li u , S.-B. (2010) Potential Distribution along UHV AC Transmission Line Composite Insulator and Electric Field Distribution on the Surface of Grading Ring. High Voltage Engineering, 36, 1442-1447. [10] Huang, D.-C., Wei, Y.-H., Z hong, L.-H., R uan, J.-J. an d Huang, F.-C. (2007) Discussion on Several Problems of De- veloping UHVDC Transmission in China. Power System Technology, 31, 6-12 . [11] Sun, C.-H., Zon g, W., Li, S.-Q., Pen g, Y.-H. and Ren, W.-W. (2006) A More Accurate Calculation Method of Surface Electric Field Intensity of Bundled Conductors. Power System Technology, 30 , 92-96. [12] Liu, G., Li, L., Zhao, X. J., Li, W.P., Li, B., Su n , Y.L. , Ji, F. and Li, J.Z. (2012) Analysis of Nonlinear Electric Field of Oil-Paper Insulation under AC-DC Hybrid Voltage by Fixed Point Method Combined with FEM in Frequency Domain. Proceedings of the CSEE, 32, 154-161 . [13] Zhen , Y.Z., Cui , X., Lu o , Z.N., Lu , T.B., Lu, J.Y., Yang, Y., Liu, Y.Q., Han, H. and Ju, Y. (2011) FEM for 3D Total Electric Field Calculation near HVDC Lines. Transactions of China Electrotechnical Society, 26, 153-16 0.
|