Engineering, 2013, 5, 37-42
http://dx.doi.org/10.4236/eng.2013.59B007 Published Online September 2013 (http://www.scirp.org/journal/eng)
Copyright © 2013 SciRes. ENG
High-Impedance Bus Differential Protection Modeling
in ATP/MODELS
Mardênnia T. S. Alvarenga, Priscila L. Vianna, Kleber M. Silva
Power System Protection Labora t ory, Departmen t of E lectrical En gi ne ering, University of Brasilia, Brasilia, Brazil
Email: mardennia@gmail.com
Received July 2013
Abstract
This paper presents a modeling of a high-impedance bus differential protection logic using the ATP (Alternative Tran-
sients Program) MODELS language. The model is validated using ATP simulations on an electrical system consisting
of a sectionalized bus arrangement with four transmission lines (TLs) and two autotransformers. The obtained results
validate the model and present some of the advantages of using this type of bus protection, such as fast and safe opera-
tion, even when under adverse conditions such as current transformers (CTs) magnetic core saturation upon the occur-
rence of external faults.
Keywords: Bus Protection; High-Impedance Differential Protection; ATP; MODELS
1. Introduction
The increasing demand for energy supplies and lower
fares cause the electricity sector to operate close to its
stability limits, which may compromise the safety of its
operation. In this context, the protection of electric power
system plays a key role in order to extinguish system
faults quickly and appropriately, preserving the integrity
of the system components, avoiding blackouts of major
proportions and preserving load as much as possible.
Among faults in electric apparatus, sub station (S E ) bus
deserves serious attention. Even though faults in these
components are not very commonabout 5%[1], its
effects are very harmful to the system, and can often lead
it to instability.
With respect to the station-bus protection, two tech-
niques are widely used: low impedance differential pro-
tection and high-impedance differential protection. The
second one is typically used in SEs with rated voltage
greater or equal to 500 kV, where buses have arrange-
ments with fixed topology and there are less occurrences
of switching mane uvers in CTs secondar y circuits.
Softwares traditionally used for analysis of protection
systems use component models dedicated to the analysis
of the power system at fundamental frequency. As a re-
sult, the transient performances of the protection systems
are not evaluated. In this way, EMTP (Eletromagnetic
Transient Programs) softwares have shown to be an ap-
propriate alternative for modeling and simulating protec-
tive relays, since they use more thorough models of the
sys te m co mponents and provide suitable environments to
link user -defined numeric relays models.
In the state-of-art of relay modeling in EMTP software,
most papers on the subject deal with the transmission
lines (TL) distance protection [2-5]. In [2], a distance
relay is modeled in EMTP program and its performance
is compared with the one of a manufactured relay. In [3]
and [4], distance protection schemes applied to three
terminals line and double circuit lines are evaluated, re-
spectively. In both researches, the relay is modeled with
the use of MODELS language of ATP. In [5], a Visual
C++ based program is implemented to obtain the FOR-
TRAN code that represents the functional blocks of the
relay, which is incorporated in a PSCAD/EMTDC simu-
lation.
To the authors’ best knowledge, there are no papers in
the state-of-art that present high-impedance bus differen-
tial protection modeling and simulation in EMTP soft-
wares, which became the motivation and objective for the
development of this paper: propose, implement and vali-
date a high-impedance bus differential protection model in
ATP for use in power system protection schemes analysis.
The proposed model of the numerical differential pro-
tection was done using MODELS language of ATP and
can be divided into four modules: signal condition, data
acquisition, phasor estimation and differential analysis.
The first one implements the model of an anti-aliasing
analog filter. The second one implements the models of
the Sample/Holder and A/D Converter. In the third mod-
ule, the phasor’s amplitude and argument are calculated
in the fundamental frequency. Finally, the high-impedance
bus differential protection logic is implemented in the
M. T. S. ALVARENGA ET AL.
Copyright © 2013 SciRes. ENG
38
fourth and last module.
The model is validated using ATP simulations on an
electrical system consisting of a sectionalized bus ar-
rangement with four transmission lines (TLs) and two
autotransformers. The obtained results validate the model
and present some of the advantages of using this type of
bus protection.
2. Fundamentals of High -Impedance Bus
Differential Protection
In order to understand the systematic of high-impedance
bus differential protection, a single bus arrangement with
four transmission lines will be used (Figure 1).
To accomplish the differential protection closed loop,
the physical parallel connection of the CTs secondary is
necessary, as shown in Figure 1. The connected CTs
must have the same ratio in order to minimize the differ-
ence in performance between them.
As shown in Figure 1, the high-impedance bus diffe-
rential relay inter nal elements are applied to the common
node of all CTs. Rsis the stabilizing resistance, which
has typical value of 2000 Ω, and determines the high-
impedance input of the relay.
The 87Z element is a sensitive, low-impedance, ad-
justable pick-up current element scaled in voltage [6].
Since the branch current formed by these two compo-
nents is low, the high-impedance bus differential relay
trip becomes dependent on voltage in its terminals.
The Metal Oxide Varistor (MO V ) is a non-linear re-
sistance connected across the high-impedance circuit to
prevent high voltage from damaging the relay and CT
circuitry [6] .
The instantaneous overcurrent relay (50) and timed
overcurrent relays (51) control the breaker opening, dur-
ing abnormal conditions of operation of the system
which cause high current magnitudes.
The high-impedance relay is set to trip based on the
relay pickup thr eshold
( )
pick up
V
. This value must be set
Figure 1. Example of high-impedance bus diff erential relay
schematic.
above the highest voltage measurement across the relay
with a completely saturated CT for external faults cond i-
tions. This ensures safety for external-fault protection.
2.1. Normal Conditions and External Faults
without CT Saturation
In Fi gure 2, CT A represents the parallel combination of
the CTs of circuits 1, 2 and 3 of the electrical system in
Figure 1 and the constant current source,
T
ˆ
I'
, represents
the sum of their secondary currents. CT B represents the
CT of circuit 4 and the constant current source
4
ˆ
I
represents the current in its secondary circuit.
In normal conditions or external fault condition with-
out CT saturation, the current source value of CT A will
be close to zero and nearly the same as the one of CT B.
Any current difference is forced through the high- im-
pedance relay. Thus, the voltage across
s
R
and the
MOV is very low:
123
ˆˆˆˆ
I'I II
T
=++
(1)
4
ˆˆ
I 0'I
T+ =
(2)
ˆ0
R
V
(3)
2.2. External Fault Conditions with CT
Saturation
In case a fault in circuit 4, the resulting current from the
parallel combination of the CTs in the circuits 1, 2 and 3
flows through TC4 and may lead to saturatio n of its core.
The voltage across the relay is the same as the one across
the series association of
with
TC
R
. Thus, the set-
ting
pick up
V
must be such that the relay will not operate
for this situation. In this case, the current through the
MOV is very low.
As shown in Figure 3, the voltage magnitude,
ˆ
R
V
,
across the relay under through-fault conditions with fully
saturated CT can be obtained as [6]:
( )
ˆ
I
f
RTC l
VRkR RTC
= +
(4)
where,
TC
R
is the CT secondary winding resistance; k
= 1 for three-phase faults and k = 2 for single-phase-
to-ground faults;
l
R
is the one-way resistance of leads;
RTC is the CTs ratio;
ˆ
I
f
is the minimum fault current.
Figure 1. Equivalent circuit of CTs for normal conditions
and external faults without CT saturation.
Br 1Br 3Br 2Br 4
Circuit 1Circuit 2Circuit 3Circuit 487B
TRI P
Bus
87Z
RS
50/51
MOV
86
86
87Z
R
S
MOV
RL
n1
RTC
n1
V
R
+
XM
n1
I
T
RL
RTC
XM
I
4
CT ACT B
M. T. S. ALVARENGA ET AL.
Copyright © 2013 SciRes. ENG
39
2.3. Internal Bus Faults
In case of bus faults, the resulting current from the paral-
lel of the CTs will be applied to the relay, as shown in
Figure 4, and the MOV will limit the voltage across the
relay at its rated voltage in order to prevent any damage
to the relay or wiring.
For numerical relays, the performance evaluation is
based on the magnitude of the estimated voltage phasor at
fundamental frequency across the stabilizing resistance.
3. High-Impedance Bus Differential Relay
Modeling
The representation of the
s
R
and MOV elements of the
high-impedance bus differential relay were made as a
resistance and a non-linear resistance (type 92) in ATP,
respectively. The
s
R
value was taken as 2000 Ω and
the MOV rated voltage as was taken as 1.3 kV. The
MOV current x voltage characteristics may be seen in
Figure 5.
Figure 3. Equivalent circuit of CTs during external bus
faults.
Figure 4. Equivalent circuit of CTs during internal bus faults.
Figure 5. Characteristic of the MOV voltage [V] x current
[A].
The use of the MODELS environment aims to
represent the numeric elements of the relay and the
transmission lines breakers opening logic. In the pro-
posed model of the relay are included the following
modules: Signal Conditioning, Data Acquisition, Phasor
Estimation and Differential Analysis. The overall block
diagram of the EMTP simulation is shown in Figure 6.
3.1. Relay Model
3.1.1. Signal Conditioning
Auxiliary CTs: The auxiliary CT is used to convert
and restrict the current values in the relay input into
suitable voltage levels for the A/D converter. Their
model is composed of an ideal transformer 1:1 and a
resistor on the secondary side, whose terminals pro-
vide the output voltage of this element. The resistance
value is dimensioned so that, for the maximum input
current, the output voltage remains within the range
of 10 to 10 V [5].
Analog Filter: The analog filter is responsible for at-
tenuating the CT’s high frequency components and
preventing the occurrence of aliasing effect in the
sampling process. In the model relay, an analog
third-order low-pass Butterworth filter is employed
[4]:
9 53369
()
(1.6510 )(2.36102.78.101.6510 )
Hs
ss s
=
++× ××
(5)
3.1.2. Data Acquisition
Sampler/Holder: It is the first stag e of the data acqu i-
sition module. It is responsible for initializing the
conversion of the analog signal into a digital signal.
This stage guarantees the signal is sampled at a rate of
16 samples per cycle (960 Hz) for the quantization
process. The building blocks of this module are ex-
ecuted every sampling period, what process is done
by setting the para meter TIMESTEP MIN: 1.0416 667
× 103.
Figure 6. High-impedance bus differential rel ay mod el.
87Z
RS
MOV
RL
n1
RTC
n1
VR
+
XM
n1
I
T
RL
RTC
CT A
87Z
RS
MOV
RL
RTC
VR
+
XM
I
T
0246810 12
x 10
4
1200
1400
1600
1800
2000
2200
2400
2600
2800
Current [A]
Voltage [V]
ATP MODELS
RE L AY 87Z
Sign al
Conditioning
T RIP
Differential
A nalys i s
Breaker 1
Data
Aquisiction P h as or
Esti m ati on
Current
S ignals
P hasors
Trip signal - Br 1
Breaker n
Br 1
Br n
i
i
R
S
MOV
T RIP
i
i
V
PICK-UP
Trip signal - Br n
M. T. S. ALVARENGA ET AL.
Copyright © 2013 SciRes. ENG
40
A/D Converter: This submodule is responsible for
quantization process of the output signal from earlier
stage. The sampled signal is converted to a 16-bit bi-
nary word with a two’s complement number system
encoding. The conversion is done by the method of
Successive Approximations. The resolution of the
converter and the digital words in the base 10 for pos-
itive and negative numbers is given, respectively, by:
21
b
Y
Res =
(6)
10
x
ZINTouRON Res

=

(7)
10
22
b
Yx
Z INTouRONY
 −
=

(8 )
where x is the model input, Y is the converter maximum
symmetrical excursion, Res is the converter resolution,
INT is the truncation op eration and RON is the rounding
operation. From de values of b + 1 = 16 and Y = 10 , one
can get the converter resolution equal to 3.0518 × 104.
The model output is the floating point (FP) equivalent of
the binary value Z10, which is given by the following
expressions:
10
·,0FPZResfor x= ≥
(9)
1
10
2 Re0
b
FPZsfor x
+

=−⋅ <

(10 )
3.1.3. Phasor Estimation
Buffer: Array used for storing the data required for
the phasor estimation algorithm. For the Modified
Cosine Filter algorithm [7] and a sampling rate of 16
samples/cycle, a 17 samples buffer is required.
Cosine Filter: In order to eliminate the decaying DC
component from the current and voltage fault signals,
the Modified Cosine filter [7] was used. The authors
of the algorithm showed that, with two consecutive
outputs of the traditional cosine filter and a correc tion
factor, it was possi ble to obtain a satisfactor y result in
the elimination of the decaying DC component.
3.1.4. Differencial Analysis
Finally, the high-impedance bus differential relay eva-
luates the voltage on its terminals based on the estimated
voltage phasors from previous staged. When the voltage
magnitude is higher than a pre-established value,
pick up
V
,
the relay sends a trip signal to the breakers in order to
isolate the fault.
3.2. Breakers
The breaker model provides the status of the breakers in
the simulated system. The real breakers opening delay
related to the time for energizing the opening coil, open-
ing the contacts and extinguishing the electric arc—is
referenced in ATP as an intentional delay. This delay is
taken as 2 cycles of the fundamental frequency, what, for
60 Hz, is equivalent to 33.333 ms. The breaker model
also guarantees that the ATP switch only opens when the
current is equal or very close to zero.
4. The Simulated Power System
For the model validation, an electrical system consisting
of a sectionalized 230 kV bus arrangement with four
transmission lines and two autotransformers was used.
The transmission lines are 100 km each and are mod-
eled as fully transposed, with distributed and constant
with frequency parameters. Two of them are connected
to Bus 1 and two of them to Bus 2. The autotransformer
1 has rated voltage of 230/69/13.8 kV, is modeled as a
saturable transformer and is connected to Bus1. The au-
totransformer 2 has rated voltage of 500/230/13.8 kV, is
modeled as a saturable transformer and is connected to
Bus 2. The CTs used are C800 1200-5 A, whose models
were reported in [8]. The resistances of CTs secondary
circuit and its cables are
TC
R 0.75=
and
TC
R2=
,
respectively.
For maximum selectivity, two protection zonesone
for each of the bus’ sectionsare used. The first one
encompasses the CTs of TLs 1 and 2, the autotransfor-
mer 1 and the CT of the tie breaker, whereas the second
one encompasses the CTs of TLs 3 and 4, the autotrans-
former 2 and the CT of the tie breaker. The substation
single line diagram with the corresponding protection
zones may be seen in Figure 7. The diagram of the pa-
rallel interconnection of the first zone CTs is shown in
Figure 8. The CTs of the second zone are connected si-
milarly.
The system’s parameters are presented in Tables 1 and
2. The first one contains the TLs’ parameters and the
second one presents the zero and positive sequence
Thévenin equivalents and the amplitude and phase of the
cosine voltage sources.
Figure 7. Diagram of the simulated power system.
Bu s 1C TCT
TL 1
Bu s 2
CT
AT 1TL 2TL 3AT 2
CT
CT
CT
CT
CT
TL 4
M. T. S. ALVARENGA ET AL.
Copyright © 2013 SciRes. ENG
41
Figure 8. CTs scheme of the high-impedance bus bar diffe-
rential protection.
Table 1. Transmission lines’ parameters.
0
[/ km]Z
1
[/ km]Z
0[μS/ km]Y
1[μS/ km]Y
TL1,TL2 0.532 + j1.541 0.098 + j0.510 2.293 3.252
TL3,TL4 0.469 + j1.289 0.098 + j0.506 2.164 3.272
Table 2. Voltage sources’s parameters.
Source V [pu]
0 [
]
1 [
]
TL1 S1 1,01
-30° 18.401 + j28.691 13.379 + j20.866
TL2 S2 1
-30° 14.242 + j22.194 10.955 + j17.072
AT1 S3 0,29
-30° 14.242 + j22.194 10.955 + j17.072
TL3 S4 1
-30° 16.068 + j25.039 12.050 + j18.779
TL4 S5 0,99
-30° 18.412 + j28.691 13.389 + j20.866
AT2 S6 2,06
-30° 16.836 + j26.236 14.177 + j22.093
By obtaining the single-phase and three-phase faults’
current contributions to the zones 1 and 2 of the consi-
dered bus of zones 1 and 2, the value of
pick up
V
can b e
calculated for each zone considering the worst voltage
scenario at the terminals of the relay:
1600.4 V
zone
pick up
V=
(11)
2539.1V
zone
pick up
V
==
(12)
5. Simulations and Results
For a performance analysis of the implemented model,
bolted three-phase simulations were performed at Bus 1
and at transmission line 3.
The zone 1 relay should trip when the voltage phasor’s
magnitude in its terminals exceeds the Vpick up value
adjusted: 600.4 V; and, similarly, the zone 2 relay should
trip when this value e xc e eds 539.1 V.
5.1. Three-Phase Fault in Bus 1
For three -phase faults in Bus 1, the maximum magnitude
of voltage phasor at the terminals of the relay exceeded
the value of 600.4 V, leading to a correct trip in zone 1,
as shown in Figures 9(a), (c) and (e). As expected, zon e
2 did not trip, as shown in Figures 9(b), (d) and (f). Th e
voltage at the terminals of the relay was safely clamped
to the MOV rated voltage of 1.3 kV. As seen in Figure 9,
due to the MOV operation, the voltage developed across
the relay was nonsinusoidal. The operating time of the
relay was 15.625 ms (o r 0. 96 cycles).
5.2. Three-Phase Fault in Transmission Line 3
From the analysis of Figures 10, the relay did not oper-
ate for an external fault on TL 3, as expected. It can be
seen that the voltage phasor magnitude was approximately
zero throughout all the simulation period, guaranteeing
the safety of the protection system. In this case, the pro-
tection scheme of transmission line 3, not included in this
paper, should operate to extinguish the defect.
(a) (b)
(c) (d)
(e) (f)
Figure 9. Voltage in relay terminals in occurrence of the
three-phase fault in bus1: (a) Phase A of zone 1; (b) Phase A
of zone 2; (c) Phase B of zone 1; (d) Phase B of zone 2; (e)
Phase C of the zone 1; (f) Phase C of zone 2.
87Z
Vpick-up
RTC RL
RTC
RTC
RTC
RL
RL
RL
ZONE1
TL 1
AT 1
CT - Bus 2
TL 2
Rs
MOV
020 40 60 80 100
-1500
-1000
-500
0
500
1000
1500
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of V [V]
V
pick-up
[V]
020 40 60 80 100
-100
0
100
200
300
400
500
600
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [ V ]
V
pick-up
[V]
020 40 6080 100
-1500
-1000
-500
0
500
1000
1500
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of V [V]
Vpick- up [V]
020 4060 80100
-100
0
100
200
300
400
500
600
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [ V ]
V
pick-up
[V]
020 40 6080100
-1500
-1000
-500
0
500
1000
1500
Time [ms]
Voltage [V]
Volta ge [V]
M agni tude of V [V]
V
pick- up
[V]
020 40 60 80100
-100
0
100
200
300
400
500
600
Time [ms]
Voltage [V]
Volta ge [V]
M agni tude of [V]
V
pick- up
[V]
M. T. S. ALVARENGA ET AL.
Copyright © 2013 SciRes. ENG
42
(a) (b)
(c) (d)
(e) (f)
Figure 10. Voltage in relay terminals in occurrence of the
three-phase fault in TL 3: (a) Phase A of the zone 1; (b)
Phase A of the zone 2; (c) Phase B of the zone 1; (d) Phase B
of the zone 2; (e) Phase C of the zone 1; (f) Phase C of the
zone 2.
6. Conclusions
This paper presented the fundamental concepts of high-
impedance bus differential protection and an innovative
approach for its modeling and simulation using the
MODELS language in ATP software. The obtained re-
sults validated the model and presented some of the ad-
vantages of using this type of bus protection.
This paper also addressed the role of protection in the
event of outbreaks in the electrical system, but the re-
search, still under development, aimed the inclusion of
more thorough analysis of the model and the protection
scheme. Some ideas for future researches include:
Analysis of high-impedance bus differential protec-
tion applied to other bus arrangements.
Inclusion of more elements to the considered bus,
such as other transmission lines, transformers, reac-
tors, shunt capacitors, among others.
Implementation of other protection schemes at the
same bus in order to compare their advantages and
disadvantages.
References
[1] P. M. Anderson, Power System Protection,” John Wiley
& Sons, Inc., Piscataway, New Jersey, EUA, 1999.
[2] W. G. C. of the Systems Protection Subcommittee of the
IEEE PSRC, “Software Models for Relays,” IEEE Trans-
actions on Power Delivery, Vol. 16, No. 2, Apr 2001.
[3] K. M. Silva, W. L. A. Neves and B. A. Souza, “EMTP
Applied to Evaluate Three-Terminal Line Distance Pro-
tection Schemes,” IPST: International Conference on
Power Systems Transients, Lyon, France, June 2007.
[4] D. N. Gonçalves, “Distance Performance Evaluation on
Transmission Lines Compensated with TCSC,” Master’s
thesis, Federal University Rio de Janeiro, 2007. (in Por-
tuguese)
[5] S. G. A. Perez. “Modeling Relays for Power System Pro-
tection Studies,” Ph.D. Dissert ation, University of Saskat-
chewan, Saskatoon, Saskatchewan, Canada, July 2006.
[6] K. Behrendt, D. Costello and S. E. Zocholl, “Considera-
tions for Using High-Impedance or Low-Impedance Re-
lays for Bus Differential Protection,Proceedings of the
35th Annual Western Protective Relay Conference, Spo-
kane, WA, 2008.
[7] D. G. Hart, D. Novosel and R. A. Smith, “Modified Co-
sine Filters,” US Pate nt 6,154,687, Nov. 2000.
[8] EMTP Reference Models for Transmission Line Relay
Testing,IEEE Power System Relaying Committee,
2004.
020 4060 80100
-100
0
100
200
300
400
500
600
700
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [ V ]
V
pick-up
[V]
020 4060 80100
-100
0
100
200
300
400
500
600
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [ V ]
V
pick-up
[V]
020 4060 80 100
-100
0
100
200
300
400
500
600
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [ V ]
V
pick-up
[V]
020 40 60 80 100
-100
0
100
200
300
400
500
600
700
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [ V ]
V
pick-up
[V]
020 40 60 80 100
-100
0
100
200
300
400
500
600
700
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [V]
Vpick- up [V]
020 4060 80100
-100
0
100
200
300
400
500
600
Time [ms]
Voltage [V]
Voltage [V ]
Ma gnitude of [ V ]
V
pick-up
[V]