Jazan area is located in the most active seismic zone region of the Kingdom of Saudi Arabia where there is a complicated geological structures and tectonics. This project reviews the seismic activities occurred in Jazan area together with reviewing the Saudi Building (Seismic) Code (SBC-301-2007) [1]. A multi-story reinforced concrete building, in Jazan city, was seismically analyzed using the Equivalent Lateral Force Procedure with the aid of STAAD PRO software. The building, which was Ordinary Reinforced Concrete Moment Resisting Frame (ORCMRF), was analyzed in compliance with the provisions of (SBC-301-2007) [1]. The most important parameters governing the analysis of this frame were dead load, live load and seismic loads. Seismic loads were computed as pairs of accelerations versus times. The damping ratio was taken as 0.05 (5% of the critical damping). The ground accelerations versus time periods were calculated using SBC-301-2007 together with parameters necessary to be used as input data for the program to calculate the seismic parameters, i.e., reactions, displacements, base shear, bending moments, shearing forces, drifts. The obtained results show effects of earthquake ground motions on building studied herein are so greater for the higher increases of the values of outputs resulting from seismic loads comparing to that due to static load only. Finally, the results obtained, clearly, show the importance of taking the Saudi seismic code provisions into account when analyzing and designing multi-story buildings in Jazan area.
Jizan, or more properly Jazan, was known in ancient times as Almikhlaf Alsulimani. Jazan is located on the southwest corner of Saudi Arabia on the coast of the Red Sea and directly north of the border with Yemen. Jazan City lies in an active zone of earthquakes classified as zone 2B with maximum applied horizontal acceleration of 0.2 g. Saudi Arabia is divided into 25 zones; each zone has its specific building code covering not only seismic activity but other criteria as well.
The Province of Jazan lies in the south west section of the Kingdom of Saudi Arabia. It has a population of approximately 1,365,110 at the 2010 census and covers an area of 40,000 km2 including some 5000 villages and cities. Jizan, is home to the Port of Jizan, Saudi Arabia’s third most important port on the Red Sea. It stretches some 300 km along the southern Red Sea coast, just north of Yemen. The region includes over 100 islands in the Red Sea. The Farasan Islands, Saudi Arabia’s first protected wildlife area, is home to the endangered Arabian gazelle and, in winter, receives migratory birds from Europe.
Many researches and studies, in this area, have been conducted relating to Saudi Arabia in general and southwestern Saudi in particular such as: S.A. Ashour and H.H. Abdel-Rahman, in 1994, who presented a paper on “Application of Seismic Risk Analysis and Earthquake Simulation Methods to the Western Region in Saudi Arabia” [
A comparative study on seismic provisions made in UBC-1997 and Saudi building code (SBC-301-2007) for RC buildings was prepared by Nazar and M. A. Ismaeil (2014) [
Awad Ali Al-Karni (2009) [
Recently, there are two independent analog seismic telemetry networks in Saudi Arabia. The King Saud University (KSU) network was established in 1985 and consists of 30 stations with denser sub-networks in the Gulf of Aqabah region (12 stations) and the southwestern part of Saudi Arabia (8 stations). A network run by King Abdulaziz City for Science and technology (KACST) was established in 1993 with 11 short-period stations in the Gulf of Aqabah and the southwestern part of Saudi Arabia adjacent to the Yemen border. Saudi Arabia will set up an additional 50 advanced earthquake monitoring stations. The King- dom already has 150 earthquake monitoring stations called the Saudi National Seismic Network (SNSN), and the new ones will boost the capability by providing precise data collection [
In 2014, a magnitude-5.1 earthquake struck in the southwestern part of the Kingdom, 50 km northeast of Jazan, at a depth of 10 km followed by 37 aftershocks of magnitudes ranging 0.94 - 5.1 in Richter scale [
Its impact was felt by inhabitants in the Asir and Najran regions. Generally, there were many earthquakes struck Jazan area and north of Yemen in the years 859, 1121, 1191, 1269, 1481, 1630, 1710, 1941, 1947 (of magnitude 6, killed 1200 of people), 1955, 1982, 1993 (of magnitude 4.8) as shown in
Geological Survey (SGS) catalogue for all years up to 2013.
The investigated building is a multi-story reinforced concrete structure used as
offices building and located in Jazan city. The elevation of the building is shown in
The dimensions of the building are 16 m in the X-Direction of equal 4-bays and 20 m in the Z-Direction of equal 5-bays. The structural system consists of rigid frames and only the XY plane frame was used in the analysis. The cross sections of the construction elements are as follows:
・ Typical columns sections = 300 mm × 300 mm,
・ Typical beams sections = 300 mm × 450 mm, and
・ Typical slab thickness = 150 mm.
The main analysis method was the modal response spectrum analysis with taking 5% damping ratio of the critical value. The analysis was performed with the STAAD-Pro software. The ground accelerations versus time periods were calculated using SBC-301-2007 provision together with other necessary parameters needed to complete the analysis.
The most important parameters governing the analysis of this frame were dead load, live load and seismic loads. As per SBC-301-2007 the following selected load combinations were selected for the analysis of the studied frame:
Load Case 1 (L/C1) is static load (dead and live):
Load Case 2 (L/C2) is static load + Earthquake loads:
Load Case 3 (L/C3) is dead + Earthquake loads:
where
f1 = 1.0 for areas occupied as places of public assembly, for live loads in excess of 0.5 kN/m2 and for parking garage live load.
f1 = 0.5 for other live loads.
In this analysis, the live load is taken as 3.5 kN/m2.
From the frame shown in
The horizontal seismic loads are defined according to Saudi Building Code (SBC-301-2007). The lateral force effect on the structure can be translated to equivalent lateral force at the base of the structure which can be distributed to different stories. According to Saudi Building Code (SBC-301-2007), the total seismic base shear force V is determined as follows:
where: Cs is the seismic coefficient, W is the total weight and V is the base shear. The seismic design coefficient (Cs) shall be determined in accordance with the following equation:
where, SDS = Design spectral response acceleration in the short period range,
R = Response modification factor,
I = Occupancy importance factor determined.
The value of the seismic response coefficient, (Cs), need not be greater than the following equation:
T = Fundamental period of the structure (sec)
But shall not be taken less than.
Design earthquake spectral response acceleration at short periods, SDS, and at 1-sec period, SD1, shall be as follows.
where:
SS: the maximum spectral response acceleration at short periods (determined from the 0.2 sec.).
S1: the maximum spectral response acceleration at a period of 1 sec.
Fa: acceleration-based site coefficient.
Fv: velocity-based site coefficient.
SMS: the maximum spectral response acceleration at short periods adjusted for site class.
SM1: the maximum spectral response acceleration at a period of 1 sec adjusted for site class.
SDS: the design spectral response acceleration at short periods.
SD1: the design spectral response acceleration at a period of 1 sec, in units of g-sec.
The design response spectra curve, as indicated in
For period less than or equal to T0, the design response spectra acceleration, Sa, shall be taken as given by:
For periods greater than or equal to T0 and less than or equal to TS, the design response spectra acceleration, Sa, shall be taken as equal to SDS:
For periods greater than TS, the design response spectra acceleration, Sa, shall be taken as equal to SDS:
where
The buildings are subjected to a lateral load distributed across the height of the building based on the following formula specified by Saudi Building Code
(SBC-303-2007):
where, Fx is the applied lateral force at level “x”, W is the storey weight, h is the story height and V is the design base shear, and N is the number of stories. The summation in the denominator is carried through all story levels. This results in an inverted triangular distribution when k is set equal to unity. A uniform lateral load distribution consisting of forces that are proportional to the story masses at each story level.
k = an exponent related to the structure period as follows:
For structures having a period of 0.5 sec or less, k = 1,
For structures having a period of 2.5 sec or more, k = 2.
The Saudi Building Code (SBC-303-2007) provides seismic maps for the Kingdom of Saudi Building.
Using the Saudi Building Code (SBC-301-2007) [
From
R = 2.5 (for ordinary R.C. resisting moment frame),
I = the occupancy importance factor determined in accordance with section 9.5 (SBC-301-2007),
I = 1 (for occupancy category I and II),
A total time of vibration of 10 seconds taken as time interval of 0.025 second was considered for the analysis.
The obtained results from the analyzing the frame were taken only for the two sections 1 and 2 as shown in
The load combination 1 (Static, dead load plus live load) (L/C1), gives maximum axial forces through section-1, which were greater in columns at floor level and decreased gradually for the highest columns respectively. A comparison
between the values of axial loads for the columns along section-1 is clearly explained in
The shear forces for the columns falling in section-2 were comprised for the three load combinations and load combination 2 (L/C2) (dead + live + seismic) gives maximum values from the ground floor to the 8th floor. Also the values of combination 3 (L/C3) showed greater than the values of combination 1 up to the 8th floor level. This is clearly shown in
City | SS | S1 | Fa | Fv | SMS | SM1 |
---|---|---|---|---|---|---|
Jazan | 0.435 | 0.124 | 1.908 | 3.428 | 0.830 | 0.425 |
SDS | SD1 | T | R | Cs req | Cs max | Cs min |
0.553 | 0.283 | 1.000 | 2.5 | 0.221 | 0.113 | 0.024 |
No. | Time Interval (sec) | Accelerations (m/s2) |
---|---|---|
1 | 1.000 | 0.283 |
2 | 2.000 | 0.142 |
3 | 3.000 | 0.094 |
4 | 4.000 | 0.071 |
5 | 5.000 | 0.057 |
6 | 6.000 | 0.047 |
7 | 7.000 | 0.040 |
8 | 8.000 | 0.035 |
9 | 9.000 | 0.031 |
10 | 10.000 | 0.028 |
For the purpose of reflecting the importance of including seismic loads, percentage difference were carried out to explain the difference between the shear forces obtained due to L/C1 and L/C2 with referred to static load. The comparison is shown in
Note that:
The bending moments for the columns falling in section-2 were compared for the three loads combinations. As for shear forces, the load combination 2 (dead + live + seismic) gave maximum values varied from the ground floor to the 8th floor. Also the values of L/C3 showed greater values than that due to L/C1 up to the 8th floor level. This is clearly shown in
As done for shear forces, percentage differences were carried out to explain the differences between the bending moments obtained due to L/C1 and L/C2 with referring to the static load. The comparison is shown in
The displacements taken here are only the horizontal displacements due to seismic loads and have the same values for the two combinations and also are same for the two sections. The maximum displacements, normally occurred, at the top of frame with a value of 76.5 mm. the values of displacements through the height of the frame can be shown in
Most buildings in Jazan area have not been analyzed and designed with compliance of the Saudi Seismic Code. Based on the obtained results from the analysis of the studied frame in Jazan city, it can be concluded that:
1) It is found that the values of horizontal support reactions generating from L/C2 were about 8 times that due to L/C1 in the outer supports and this rate increases much more in the inner supports.
2) It is clearly observed that the calculated resultant of nodal displacements due to L/C2 was about 6 to 8 times the nodal displacements due to L/C1.
3) Axial forces of columns due to L/C1 are slightly greater than that due to L/C2 and these forces decrease gradually in the upper floor columns.
4) The shear forces obtained in the ground floor level due to seismic loads (L/C2) were about four times of that obtained due to static loads only (L/C1).
The increasing varies gradually from 1.6 (160%) times for the first level to 0.14 (14%) at the 7th level. For levels 8th, 9th and 10th, the values of shear forces due to static loads are greater than that due to seismic loads.
5) The maximum bending moments obtained due seismic load were approximately found to be eight times of that obtained by using static loads. As in the shear forces, the values of bending moments due seismic loads (L/C2) are greater through the floor heights, varied from 166% to 16% between 1st level to 8th level. For levels 9th and 10th the bending moments due to static load showed greater values.
Hassaballa, A.E., Adam, F.M. and Ismaeil, M.A. (2017) Seis- mic Analysis of a Ten-Storey Reinforced Concrete Building in Jazan Area, KSA. Open Journal of Civil Engineering, 7, 252-266. https://doi.org/10.4236/ojce.2017.72016