The electric networks for the distribution to low voltage costumers can be configured in different layouts. Two main approaches are used: the European system composed by three-phase distribution transformers or the North American system composed by single-phase distribution transformers and three-phase transformer banks of single-phase transformers. With respect to harmonic analysis, much more attention has been focused on the three-phase balanced systems arrangements than on the unbalanced four-wire delta system extensively used to supply low voltage loads of 120/240 V. Different authors have shown the three-phase power systems modeling on a phase-coordinates frame. However, the presence of significant asymmetries in the network forces the need of adding a new phase-coordinates model to represent the three-phase transformers banks of two or three single-phase transformers in its various connections. Several papers treat the use of harmonic analysis programs based on a phase-coordinates frame to study the Wye or Delta connected three-phase systems. However, the commonly used four-wire delta connected systems are not fully treated in literature. This paper presents a phase-coordinates model for the representation of the commonly used three-phase transformer banks of three or two single-phase transformers, and single-phase distribution transformers for the harmonic analysis of the four-wire delta connected systems. The harmonic analysis method based on the presented model is used to examine the characteristics of this kind of distribution system with respect to the penetration of harmonics currents from loads to the primary system.
The electric networks for the distribution to low voltage costumers can be configured in different layouts. Two main approaches are used: the European system composed by three-phase distribution transformers or the North American system composed by single-phase distribution transformers and three-phase transformer banks of single-phase transformers. With respect to harmonic analysis, much more attention has been focused on the three-phase balanced systems arrangements than on the unbalanced four- wire delta system extensively used to supply low voltage loads of 120/240 V. The phase- coordinates models can be used for the analysis of distribution systems at fundamental frequency as well as for other frequencies and are well suited for the harmonic analysis of unbalanced networks.
The formulation of the harmonic power flow method in a phase-coordinates frame, besides allowing for a more accurate modeling of unbalanced networks, allows the specification of harmonic injections of any type: single-phase or three-phase of the desired sequence. Therefore, it is possible to study the effect of the non-linear loads according to its features and connection to the circuit.
Different authors have shown the three-phase power systems modeling on a phase- coordinates frame [
Several papers treat the use of harmonic analysis programs based on a phase-coor- dinates frame to study the Wye or Delta connected three-phase systems [
One of the most widely used techniques for solving the harmonic power flow problem is the so called harmonic penetration study [
The magnitude and phase angle of each of these current sources are calculated by the results of a previously solved fundamental frequency power flow and considering the typical harmonic spectrum of the non-linear loads presented in the system [
The procedure lies in the concept that the wave forms of the non-linear loads distorted currents are independent of the voltage magnitude and wave form. In that way, a fixed relation between each harmonic current component and the fundamental frequency current is considered.
Thus, the magnitude and phase angle of the hth harmonic are related with the fundamental frequency current and the typical harmonic spectrum of the load by:
Once all the harmonic current injections are calculated, the resulting harmonics voltages on the system buses are determined by means of:
where V(h), Z(h) and I(h), are the voltages vector, the bus impedance matrix and the injected currents vector for each hth harmonic frequency.
The method decouples the voltages calculation for each frequency, so the process can be cyclically repeated for every harmonic frequency presented on any of the non-linear loads.
Concluded the harmonic penetration study, a complete set of harmonic voltages on every bus is obtained and with it, all the harmonic branch currents can be calculated.
The network bus impedance matrix for each frequency is determined as the inverse of the bus admittance matrix Y(h) that is built from established models for the different elements of the electrical system [
Using the positive, negative and zero sequence models of the system’s elements the bus impedance matrices of different sequences can be found.
However, some types of electrical distribution networks of industrial, commercial or service facilities are so unbalanced that a more effective modeling can be achieved by using phase-coordinates models.
In essence, the phase-coordinates modeling is able to determine the voltage at all the nodes with respect to a reference node, which is usually the ground, but in the case of a not grounded system, or an asymmetric network as the four-wire delta connected system is a fictitious reference node.
Again, the resulting harmonics voltages of the system nodes are determined by means of (3). Thus, the key elements in the analysis are the determination of the vector I(h) and the matrix Z(h) in the phase-coordinates frame.
The harmonic power penetration analysis in phase-coordinates allows the specification of current injections of any type: single-phase or three-phase of the desired sequence. Therefore, it is possible to study the effect of non-linear loads according to their characteristics and their connection to the circuit.
In order to represent a non-linear load current injection of N phases, a typical harmonic spectrum of equal number of phases must be used.
The fundamental apparent power S(1) of the load is the sum of the power of each phase n:
On the other hand, as the magnitude and phase angle relations between the fundamental currents of the N phases of the typical harmonic spectrum must be fulfilled, it can be expressed a linear relation between each phase fundamental current and their correspondent phase fundamental current in the considered harmonic spectrum.
To determine the complex parameter μ, the relation (5) is substituted in (4) obtaining:
From where:
Calculated μ, the fundamental and other harmonic currents of each phase can be obtained by:
where fμ represents the phase angle of μ.
Normally, typical harmonic spectrums are employed to represent the non-linear loads currents injections, however, a non-typical harmonic spectrum can be employed to represent a non-typical operation condition of the harmonic producing loads: partial load, voltages unbalance, non-characteristic harmonics generation, etc.
To determine the bus impedance matrix for every frequency, there network nodal admittance matrix for each frequency must be formed, which comprises the adding of the nodal admittance sub-matrices of different elements such as the transformers, feeders, machines and other passive elements such as capacitor banks, harmonic filters, etc.
The model of three-phase transformers and three-phase transformer banks is one of the most complicated parts of the network model, due to the diversity of their connections and configurations. However, the effective network overlapping technique presented by Chen [
In [
where ZFULL represents the full-winding impedance and ZHALF the half-winding impedance of the distribution transformer.
Taken into account that the series reactance of the transformer varies with the harmonic order h, and considering the commonly employed values for the half-winding impedance of the transformer [
where R and X are the full-winding resistance and reactance of the transformer at the fundamental frequency.
Using that model, this paper presents the admittance matrices of the commonly used three-phase transformer banks configurations. Besides, for each type of transformer bank, an analysis of the harmonics penetration in the primary circuit is achieved to highlight the characteristics of this system.
The floating Wye-Delta transformer bank (
The admittance matrix of this transformer bank considering a relation m between the primary and the secondary winding impedances of the lighting?leg transformer (1) is:
where yPP, yPS and ySS of each transformer are calculated as follows:
And y0 is the admittance shunt that represents the non-load losses and y is the series full-winding admittance of the transformer (both calculated for the frequency h), while α and β are the corresponding tap selection for primary and secondary respectively.
The open Wye-open Delta transformer bank (
The admittance matrix of this transformer bank considering a relation m between the primary and the secondary winding impedances of the lighting?leg transformer (1) is:
The single-phase distribution transformer (
The admittance matrix of this transformer, provided that the primary neutral is grounded, is:
The presented phase-coordinates model has been implemented in a Matlab 2010 application to evaluate the harmonics penetration from the low voltage four-wire delta connected non-linear loads into the primary medium voltage feeder of a grounded Wye connected distribution system.
The test system of
At the buses N1, N2 and N3 (250 meters apart each other) three equal transformer banks supply the loads at the low voltage buses n1, n2 and n3 that consists in a mixture of 240 V three-phase and 120 V single-phase loads.
Two types of single-phase distribution transformers are employed to form the transformer banks (
In order to evaluate the harmonic injections effect of the non-linear loads, only this kind of loads will be considered in the example cases. The data of the loads supplied at the low voltage buses are (
These non-linear loads have been represented by the typical harmonic spectrum (
Three cases are analyzed:
1) Three floating Wye-Delta transformers banks.
2) Three open Wye-open Delta transformers banks.
3) Three single-phase distribution transformers.
All the currents and voltages that will be shown are in per unit values of 100 kVA bases.
Transformer | Primary | Secondary | kVA | R (%) | X (%) |
---|---|---|---|---|---|
Lighting-leg | 2400 V | 120/240 V | 100 | 1.0 | 3.0 |
Power-leg | 2400 V | 240 V | 50 | 1.0 | 3.0 |
Load | Voltage | Phases | kW | Power factor | Type |
---|---|---|---|---|---|
1 | 240 V | 3-phase | 10 | 0.866 | Six pulse converter |
2 | 120 V | 1-phase | 20 | 0.900 | Computers |
h | hf (Hz) | Computer load | Three-phase converter (six pulse) | ||||||
---|---|---|---|---|---|---|---|---|---|
Ih (%) | fh (deg) | Iah (%) | fah (deg) | Ibh (%) | fbh (deg) | Ich (%) | fch (deg) | ||
1 | 60 | 100.0 | −37.0 | 100.0 | −40.7 | 100.3 | −160.8 | 100.1 | 79.1 |
3 | 180 | 65.7 | −97.0 | 0.1 | 112.3 | 0.1 | −128.6 | 0.1 | 2.8 |
5 | 300 | 37.7 | −166.0 | 20.4 | −26.1 | 20.3 | 93.8 | 20.4 | −146.4 |
7 | 420 | 12.7 | 113.0 | 8.2 | −98.6 | 8.3 | 141.1 | 8.2 | 20.6 |
9 | 540 | 4.4 | −46.0 | 0.1 | 3.7 | 0.1 | −178.6 | 0.0 | −1.6 |
11 | 660 | 5.3 | −158.0 | 3.5 | −90.9 | 3.5 | 28.4 | 3.6 | 148.0 |
13 | 780 | 2.5 | 92.0 | 2.9 | −166.6 | 3.0 | 73.3 | 2.9 | −47.3 |
15 | 900 | 1.9 | −51.0 | 0.0 | −100.2 | 0.0 | 132.6 | 0.0 | −1.6 |
17 | 1020 | 1.8 | −151.0 | 0.3 | 104.7 | 0.3 | −137.3 | 0.3 | −13.5 |
19 | 1140 | 1.1 | 84.0 | 0.4 | 103.9 | 0.4 | −16.1 | 0.4 | −134.6 |
In this case, three floating Wye-Delta transformers banks are used with the following connections (
Bank | Transformers | Primary | Secondary | kVA | |||||
---|---|---|---|---|---|---|---|---|---|
Bus | Phases | Bus | Phases | ||||||
1 | Lighting-leg | N1 | A | Neutral | n1 | A | B | AB* | 100 |
Power-leg | N1 | B | Neutral | n1 | B | C | 50 | ||
Power-leg | N1 | C | Neutral | n1 | C | A | 50 | ||
2 | Power-leg | N2 | A | Neutral | n2 | A | B | 50 | |
Lighting-leg | N2 | B | Neutral | n2 | B | C | BC* | 100 | |
Power-leg | N2 | C | Neutral | n2 | C | A | 50 | ||
3 | Power-leg | N3 | A | Neutral | n3 | A | B | 50 | |
Power-leg | N3 | B | Neutral | n3 | B | C | 50 | ||
Lighting-leg | N3 | C | Neutral | n3 | C | A | CA* | 100 |
*AB, BC or CA is the mid-tap phase in the lighting-leg transformer.
Single phase non-linear loads are supplied by the lighting leg transformers. If the both secondary sections of each lighting-leg transformer supply half of the single-phase load, no current flows through the mid tap.
Due the floating primary neutral, the summation of primary currents must be zero. So, it can be shown, that the primary currents in the nodes 1, 2 and 3 (
where k is the transformer relation and IL1 is the current of the single-phase load that is connected to the lighting-leg transformer secondary.
Considering the expression (18), all the single-phase load harmonic currents will flow through the transformer bank and so harmonics of all sequences will appear in the primary currents. The obtained results for the first transformer bank (
On the other hand, the flow through the feeder of the harmonics produced for all the single-phase loads is presented (
As it can be seen (
With regard to the harmonics of the secondary voltages, those are influenced by the connection of the single-phase non-linear load and the type of lighting-leg transformer employed.
If the single-phase non-linear load is equally divided between the both secondary sections of the lighting-leg transformer, the harmonics of the line to line voltages at the secondary are equal in the both secondary sections of this transformer (
However, if all the single-phase non-linear load is connected between the phases A and AB (mid tap between A and B), the line to line voltages at the secondary depend on the windings construction of the lighting-leg transformer. The obtained results are shown in
As it can be seen (
The penetration of the balanced three-phase non-linear load harmonics in the primary feeder (
With respect to the harmonics in the secondary line to line voltages, it can be seen (
In this case, three open Wye-open Delta transformers banks are used with the following connections (
Bank | Transformers | Primary | Secondary | kVA | |||||
---|---|---|---|---|---|---|---|---|---|
Bus | Phases | Bus | Phases | ||||||
1 | Lighting-leg | N1 | A | Ground | n1 | A | B | AB* | 100 |
Power-leg | N1 | B | Ground | n1 | B | C | 50 | ||
2 | Lighting-leg | N2 | B | Ground | n2 | B | C | BC* | 100 |
Power-leg | N2 | C | Ground | n2 | C | A | 50 | ||
3 | Power-leg | N3 | A | Ground | n3 | A | B | 50 | |
Lighting-leg | N3 | C | Ground | n3 | C | A | CA* | 100 |
*AB, BC or CA is the mid-tap phase in the lighting-leg transformer.
In this transformer bank, the single-phase load currents only flow through the lighting- leg transformer, so the entire effect of this harmonics is produced on the primary phase in which the lighting-leg transformer is connected (
As the single-phase load harmonics flow freely through the lighting-leg transformers, the triples harmonics penetrate the primary feeder and are added to the current in the multi-grounded neutral conductor (
In a perfectly balanced case like the presented, the triples and non-triples harmonics will be balanced in the feeder’s phases after the addition of the primary currents of the three transformer banks. On the other hand, the triples harmonics contents of the neutral current are always increasing.
With respect to the three-phase load effect, it is supplied by the two transformers, so the harmonics of all frequencies penetrate two phases and the neutral of the primary feeder (
In the presented case, the positive and negative sequence harmonics will be balanced in the feeder’s phases after the addition of the primary currents of the three transformer banks (
In this case, three single-phase distribution transformers are used with the following connections (
In this case, the load current only flow through the lighting-leg transformer, so the entire effect of this harmonics is produced on the primary phase in which the lighting- leg transformer is connected (
As the single-phase load harmonics flow freely through the lighting-leg transformers, the triples harmonics penetrate the primary feeder and are added to the current in the multi-grounded neutral conductor (
With respect to harmonic analysis, the four-wire delta connected system has the handicap that the single-phase 120 V load is connected only to the lighting-leg transformer.
Transformer | Transformer | Primary | Secondary | kVA | |||||
---|---|---|---|---|---|---|---|---|---|
Bus | Phases | Bus | Phases | ||||||
1 | Lighting-leg | N1 | A | Neutral | n1 | A | B | AB* | 100 |
2 | Lighting-leg | N2 | B | Neutral | n2 | B | C | BC* | 100 |
3 | Lighting-leg | N3 | C | Neutral | n3 | C | A | CA* | 100 |
*AB, BC or CA is the mid-tap phase in the lighting-leg transformer.
So, this system is very unbalanced by its structure and the harmonics cancellation is rarely obtained. That is why harmonics of all the frequencies can be found in the feeder phases.
The use of both the open Wye-Delta transformer banks and the single-phase distribution transformers permits the zero sequence harmonics circulation through the multi-grounded neutral conductor of the primary feeder.
The phase-coordinates model developed for the harmonic analysis is able to represent with good accuracy unbalanced networks like the presented. Their results permit the evaluation of the influence on the secondary line to line voltages of the unequal load in both sections of the secondary of the lighting-leg transformer considering its windings construction.
The authors acknowledge the Institute of Technology Galileo of Amazon (ITEGAM) and the Amazonas Research Foundation (FAPEAM) for the financial support as doctorate grant for performing this work.
Leite, J.C., Azevedo, M.S.S., Bezerra, U.H., Abril, I.P. and de León Benítez, C.A. (2016) Harmonic Propagation from the Low Voltage Four-Wire Delta Systems. Journal of Power and Energy Engineering, 4, 1-19. http://dx.doi.org/10.4236/jpee.2016.412001